Installation
62
AFDR-SVN001D-EN
Table 17. Non-compressor specific parameters
ID
Description
Values
0-03
Region Settings
[1] North American
0-20
Display Line 1.1 Small
[1612] Motor Voltage
0-24
Display Line 3 Large
[1617] Speed [RPM]
0-40
[Hand on] Key on LCP
[0] Disabled
0-41
[Off] Key on LCP
[0] Disabled
0-60
Main Menu Password
999
0-61
Access to Main Menu w/o Password
[1] LCP: Read Only
1-03
Torque Characteristics
[0] Compressor Torque
1-71
Start Delay
2s
1-73
Flying Start
[0] Disabled
1-78
Compressor Start Max Speed [Hz]
20Hz
1-79
Compressor Start Max Time to Trip
10s
1-87
Trip Speed Low [Hz]
25Hz
3-02
Min Reference
30Hz
3-13
Reference Site
[1] Remote
3-15
Reference 1 Source
[0] No Function
3-41
Ramp 1 Ramp Up Time
10s
3-42
Ramp 1 Ramp Down Time
10s
4-10
Motor Speed Direction
[0] Clockwise
4-12
Motor Speed Low Limit [Hz]
30Hz
4-18
Current Limit
107%
8-01
Control Site
[2] Controlword only
8-03
Control Timeout Time
15s
8-04
Control Timeout Function
[2] Stop
8-30
Protocol
[2] Modbus RTU
8-31
Address
3
8-82
Baud Rate
[7] 115200 Baud
14-00
Switching Pattern
[1] SFAVM
14-03
Overmodulation
[0] Off
14-10
Mains Failure
[4] Kinetic Back-up
14-12
Function at Mains Imbalance
[3] Derate
14-21
Automatic Restart Time
8s
14-50
RFI Filter
[0] Off
14-51
DC Link Compensation
[1] On
14-60
Function at Over Temperature
[1] Derate
14-61
Function at Inverter Overload
[1] Derate
14-62
Inv. Overload Derate Current
75%