Trane AFD145CLFR000D Скачать руководство пользователя страница 1

Whole House Electronic Air Cleaner

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with this unit.

Please return to service information pack upon completion of work.

Service Facts

This information is for use by individuals having adequate
backgrounds of electrical and mechanical experience. Any
attempt to repair a central air conditioning product may re-
sult in personal injury and/or property damage. The manu-
facturer or seller cannot be responsible for the interpreta-
tion of this information, nor can it assume any liability in con-
nection with its use.

CELLS. Allows access to the COLLECTION CELLS, FIELD
CHARGER and PRE-FILTER.

6) TRANSFORMER

 - supplies 24 Volts to the indoor unit and Air

Cleaner 

(not available with 50 Hz units)

7) 24 VOLT POWER / CONTROL CABLE

8) GASKET, LITERATURE AND HARDWARE PACKET

9) UPFLOW AIR HANDLER BAFFLE

 - This baffle is only included

with Air Handler models.  See note below.

NOTE:

Be careful not to discard the baffle.  It is located under
the collection cells in the shipping box.

2

2

2

2

2

3

3

3

3

3

4

4

4

4

4

5

5

5

5

5

7

7

7

7

7

6

6

6

6

6

8

8

8

8

8

3

3

3

3

3

1

1

1

1

1 2

2

2

2

2 3

3

3

3

3

RECONNECT ALL GROUNDING DEVICES.

All parts of this product that are capable of conducting elec-
trical current are grounded.  If grounding wires, screws,
straps, clips, nuts, or washers used to complete a path to
ground are removed for service, they must be returned to their
original position and properly fastened.

AIR

FLOW

1

WARNING

!

© Trane 2011

CAUTION

!

Air Handler Models

*FD175CLAH000D
*FD215CLAH000D
*FD235CLAH000D
*FD260CLAH000D

Downflow Furnace Models

*FD14DCLFR000D
*FD17DCLFR000D
*FD21DCLFR000D
*FD24DCLFR000D

Upflow Furnace Models

*FD145CLFR000D
*FD175CLFR000D
*FD210CLFR000D
*FD245CLFR000D

50 Hz Air Handler Models

TFD215CLAH005D
TFD235CLAH005D
TFD260CLAH005D

* May be "A" or "T"

9

9

9

9

9

1) PRE-FILTER

 - traps large particles such as hair and lint before

they can enter the COLLECTION CELL section.

2) FIELD CHARGER

 - Charges the contaminants.  

Only to be

serviced by a qualified technician.

3) COLLECTION CELL (2)

 - removes and collects  very small

impurities from the air.

4) CABINET

 - mounts between the furnace/air handler and return

air duct work and houses the COLLECTION CELLS, FIELD
CHARGER and PRE-FILTER.

5) POWER DOOR 

- the solid state power supply components

that convert the 24 Volt AC to the high-voltage, direct current
required to power the FIELD CHARGER and COLLECTION

1

1

1

1

1

COMPONENTS OF THE AIR CLEANER

EAC- SF- 1 3

Содержание AFD145CLFR000D

Страница 1: ...6 6 6 6 6 8 8 8 8 8 3 3 3 3 3 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 RECONNECTALLGROUNDINGDEVICES All parts of this product that are capable of conducting elec trical current are grounded If grounding wires screws straps clips nuts or washers used to complete a path to groundareremovedforservice theymustbereturnedtotheir original position and properly fastened AIR FLOW 1 WARNING Trane 2011 CAUTION Air Hand...

Страница 2: ...ntrol wiring per Figure 2 NOTE For non Trane American Standard Heating Air Conditioning systems order a 120 VAC to 24 VAC transformer KIT BAYTRANS12024 to provide 24 volt power only to the air cleaner Access to 120 VAC outlet is required Connect the power control wiring per Figure 3 NOTE Trane American Standard Heating Air Conditioning Communicating Furnaces require KIT BAYACCECOMM101 NOTE Wiring ...

Страница 3: ...hrough 1608 dated December 2006 D BLUE GREEN BROWN BLACK RED WHITE BLUE GREEN BROWN BLACK RED WHITE BLUE BROWN BROWN Data Line BLACK GRD RED Unused Unused GREEN WHITE Air Handler may not have a Low Voltage Terminal board Connect Electronic Air Cleaner wires to the Air Handler Low Voltage Color coded wires Install Transformer one is supplied with the Electronic Air Cleaner in the Furnace or Air Han...

Страница 4: ...e red jumper wire which is attached from EAC to R on the Communicating Systems PCB Confirm it is connected If there is not a jumper wire installed then one must be installed in this location in order for the air cleaner to function properly 5 Replace the Communicating control box cover 6 Locate the white wire coming from the Communicating System Air Handler PCB labeled EAC The wire will have a mal...

Страница 5: ... POWER BEFORE SERVICING COULD RESULT IN DEATH OR SERIOUS INJURY ELECTRICAL CONNECTIONS TO A STANDARD 24 VOLT AIR HANDLER GAM5 A TAM4 A TAM7 Field wiring O R B YI W1 YO Y2 BK G W2 W3 In Out O R B YI W1 YO G W2 W3 For use with Whole House Air Cleaner RED BLUE GREEN BLACK GRD Air Cleaner Plug BROWN Future Use Power Control Wiring Cable and Plug Unused WHITE For use with Whole House Air Cleaner RED BL...

Страница 6: ...om the air cleaner wire harness to earth ground by attaching the wire to a grounded screw that is connected to the metal air handler chassis or control plate assembly 7 The Green and White wires on the air cleaner wiring harness are unused in this application and should be insulated separately 8 Replace the blower access panel 9 Reconnect electrical power to the air handler 10 Check air cleaner an...

Страница 7: ...NECTIONS TO A COMMUNICATING FURNACE IN 24 V MODE 9 Attach the blue wire from the air cleaner wiring harness to the open tab on the piggyback terminal supplied in the BAYACCECOMM101 Attach piggyback terminal to the 35VA transformer terminal C Common 10 Insert the 12 blue stripped wire under the terminal strip screw marked B C on the IFC control board If the applica tion also includes an outdoor uni...

Страница 8: ...air cleaner onto the IFC platform where the 35VA transformer was previously located Use the sheet metal screws supplied with the air cleaner to mount the 50VA transformer Reconnect the 115V and 24V wires that were connected to the 35VA transformer onto the 50 VA transformer 6 Connect Red stripped wire to R terminal on the furnace control board 7 Connect Blue stripped wire to B terminal on the furn...

Страница 9: ...ogether Oil burner primary TT contacts must be isolated using field supplied relay RLY00925 or equivalent NOTE 3 The black wire Bk from ACCE unit must be connected to chassis ground to ensure proper operation R1 R1 THERMOSTAT AIR CLEANER AIR CLEANER VARIABLE SPEED OIL FURNACE TO AIR CLEANER OIL BURNER PRIMARY NOTE 3 NOTE 2 NOTE 2 NOTE 1 Y Y1 Y Y2 R RC R RC G W1 B RH G W1 BCC T T R O BR G W B Bk GN...

Страница 10: ...nal air cleaner added See the wiring diagrams for information on how to attach the wires in a two whole house air cleaner system The figure on the top of page 10 shows the wiring hookup for two whole house air cleaners attached to a furnace in conventional 24 V mode The figure on the bottom of page 10 shows the wiring hookup for two whole house air cleaners attached to a furnace in communicating m...

Страница 11: ... 11 Service Facts FIELD SUPPLIED 50 VA TRANSFORMER FIELD SUPPLIED 75 VA TRANSFORMER ELECTRICAL CONNECTIONS FOR DUAL WHOLE HOUSE AIR CLEANERS AND FURNACE IN CONVENTIONAL 24V MODE ELECTRICAL CONNECTIONS FOR DUAL WHOLE HOUSE AIR CLEANER AND FURNACE IN COMMUNICATING MODE ...

Страница 12: ...red in actual run time of the indoor fan The factory setting is 2 months 10 weeks Figure 5 Four Yellow LED s indicate the COLLECTION CELL cleaning interval This is measured in actual run time of the indoor fan The factory setting is 6 months 31 weeks See Figure 6 The three Red LED s indicate the power level setting The default setting is maximum See Figure 7 SET UP MODE OF OPERATION To enter the S...

Страница 13: ...Ds lockout mode FAULT CODES RETRIEVAL To retrieve the last three faults that the Air Cleaner Control has detected enter the SET UP mode of operation Press and hold the POWER button and the RESET button for a minimum of five seconds When the control enters the SET UP mode of operation some of the Green Yellow and Red LEDs will be on The color and number of LEDs that are on indicates how the control...

Страница 14: ...hich causes an air cleaner shuts down before the power output reaches 5 KV ON OFF OFF ON OFF OFF Device Count Check for arcing through the Collection Cells and Field Charger cases Check door operation by referring to Testing the Power Door on page 17 of the air cleaner s Service Facts 108 HV too LOW ON OFF OFF ON ON OFF Device Count Remove power door and recheck high voltage if still low replace p...

Страница 15: ...ilters are not reintroduced into the air Persons highly sensitive to the collected particles should wear appropriate respiratory protection while cleaning PRE FILTER It is time to clean the PRE FILTER when the red PRE FILTER light is illuminated 9 PRE FILTER RESET CLEAN Red light indicates that it is time to clean the COLLECTION CELLS Red light indicates that it is time to clean the PRE FILTER Cle...

Страница 16: ...otify the homeowner to clean the COLLECTION CELLS every six months 31 weeks of actual run time of the Air Cleaner This notification can be changed by the installer homeowner to 2 months 4 months 6 months or 9 months 10 20 31 or 46 weeks depending on the conditions in the home pets smokers etc Please see SET UP MODE page 3 to change the factory settings 2 Once vacuuming is completed on one side of ...

Страница 17: ...ng a low pressure water spray such as a sink sprayer or garden hose Residue like tobacco smoke may require warm water to be removed Alternate Cleaning Option For Homeowners with 200 or 200 1 COLLECTION CELLS ONLY Vacuuming the PRE FILTER and COLLECTION CELLS restores them to a high efficiency However some environmental conditions like tobacco smoke cause the COLLECTION CELLS to need to be washed w...

Страница 18: ...R LED turns off 1 to 2 seconds To reset the Collection Cell timer press and hold the RESET button until the COLLECTION CELL LED s turn off 4 to 5 seconds In a communicating system the filter reset timers can also be reset at the communicating comfort control If two air cleaners are connected on the same system reset all timers on both air cleaners at the same time to the same settings The comfort ...

Страница 19: ...t ohm meter per their manufacturers instructions 5 Touch the tip of the High Voltage Probe to the Power Door High Voltage terminal and read the volt meter 6 If the voltage read during this test is 9 6 KV or 600 volts the Power Door is working correctly Replace Power Door with a new Power Door if the high voltage is not correct 7 Turn off the Air Cleaner by pushing the POWER button 8 Remove the wir...

Страница 20: ...should arc across the paper When the arc occurs the High Voltage Supply will shut down and stay off for one minute 7 Turn off the Air Cleaner by pushing the POWER button 8 Remove the wire and tape used to defeat the interlock switch 9 If the arc occurred when the end of the paper was near or touching the Power Door High Voltage terminal during this test the Power Door assembly is OK If no arc occu...

Страница 21: ...nspect the Field Charger assembly and Collection Cells for any foreign material that may be lodged in them Clean as needed reassemble and test 4 If the Air Cleaner still does not work remove Power Door from the Air Cleaner housing 5 With the indoor blower running and the power cord plugged into the Air Cleaner use a tool to activate the Power Door interlock switch Push the power button once The fi...

Страница 22: ...ntinuously Is the amber light blinking the system device count or a fast flash Correct control wire problem Component Failure Evaluation Go to 24 Volt troubleshooting flow chart Go to Communicating Mode troubleshooting flow chart Correct control wire problem YES NO Return YES 24VAC Mode Intended YES NO COM Mode Intended NO NO YES D BLUE GREEN BROWN BLACK RED WHITE BLUE GREEN BROWN BLACK RED WHITE ...

Страница 23: ...ove the power door install the collection cells and re install the power door Replace both collection cells Air cleaner is operating correctly The power door and collection cells operate correctly Wait 10 seconds Replace the field charger Power the air cleaner with 24VAC and establish a G call from T Stat Bypass the 10 minute time delay This is done by entering and exiting the set up mode Does Gre...

Страница 24: ...nit Comfort controll is displaying a ERROR CODE 91 Like the furnace and air handler s users interfaces the air cleaner stores fault codes Check air cleaner COM light for device count one blink for each communicating device on the COM bus If device count is present ensure air cleaner green light blinks slow with indoor blower operation Clear fault log NO YES YES YES NO Is the COM LED flashing fast ...

Отзывы: