Pre-Installation
VFDB-SVX001A-EN
35
Lift Input Starter
The lifting angles hold the starting/junction cabinet
together to prevent separation and damage while riggers
move the drive to the final installation area.
The lifting angles are shipped with the starting/junction
cabinet and must be secured before lifting the cabinet.
1. Remove the lifting angles from the skid.
2. Remove the attachment hardware that is pre-installed
in the mounting holes in the top plate of the cabinet
before shipment.
3. Align and secure the lifting angles in four places as
shown in below figure.
4. Re-install the hardware (M12 x 2) and the pre-installed
attachment hardware (M6) in the mounting holes (to
seal the holes) on the top of the drive.
Storage
If the storage of the equipment is longer than one year, it
is recommended to power up once a year.
If equipment containing electrolytic capacitors (like power
supplies, power cells, etc.) is stored (unpowered) under
normal storage temperatures and conditions, it can be
kept up to 15 years.
Storage the drive in a dry, clean, and cool area.
The storage temperature must be maintained between -
40...+70 °C (-40...+158 °F). This temperature rating applies
only to the drive, it does not include the UPS
(Uninterruptible Power Supply). If the storage
temperature fluctuates significantly or if the relative
humidity exceeds 95%, use heating and moisture
protection devices to prevent condensation.
Store the drive in a conditioned building with adequate air
circulation. Do not store the drive outdoors.
Figure 24.
Overhead lifting (isolation transformer
cabinet)
U-rings
Steel cable
Lifting provision
Minimum height of
1.5 m (5 ft)
45° maximum
Figure 25.
Overhead lifting (starting/junction cabinet)
NOTICE
Equipment Damage!
Failure to follow storage recommendations could result
in equipment-only damage. Read this section carefully
and follow all recommendations for drive storage.
M12 bolt
Washer
Minimum height of
1.5 m (5 ft)
45°
maximum
Lifting Angle pair