MS-SVN003-EN
9
Indoor unit pipe
Torque wrench
Flare nut
Connection pipe
Wrench
(adjustable).
Figure 18
Flare Nut Tightening Torque
Flare nut/Piping size
Tightening torque
kg
f
, - cm
lb
f
-in
6.35 mm (1/4”) dia.
150~200
130~170
9.53 mm (3/8”) dia.
350~400
300~340
12.7 mm (1/2”) dia.
500~550
430~470
15.88 mm (5/8”) dia.
600~650
520~570
Remote Control Installation
Locate and attach the wireless
remote control as follows:
1. Do not place the control and the
remote control near heat sources
or expose to the direct rays of the
sun.
2. Do not expose the control to the
indoor unit’s supply air stream.
3. Do not place in a confined space.
4. Attach the remote control holder
as shown in Figure 19.
Evacuation and Refrigerant
Charge
1. Air Evacuation and Charging
1. Remove the cap and connect the
gauge manifold and the vacuum
pump to the charging port using
the service hoses (Figure 20).
2. Pump the indoor unit and the
connecting pipes until the
pressure in them lowers to below
1.5 mmHg of vacuum.
3. Stop the vacuum pump and close
the gauge manifold valve.
4. Remove the blanking caps and
fully open the service valves with
a hexagon wrench (Torque: 70
to 90 kg
f
- cm).
Remote
Control
Unit
ON OFF
Remote Control Holder
Tapping Screw
(small)
Wireless Remote Control
Figure 19
Содержание ADAMO MCW 5097BA00
Страница 1: ...ADAMO Installation Manual Split System Wall Type MCW Series 50 Hz MS SVN003 EN January 2003...
Страница 12: ...12 MS SVN003 EN Wiring Diagram...
Страница 14: ...14 MS SVN003 EN Notes...