MS-SVN003-EN

A good flare should have the
following characteristics:

-

Inside surface is glossy and
smooth.

-

Edge is smooth.

-

Tapered sides are of uniform
length.

Bending

5. When bending the tube, be careful

not to crush it. To prevent crushing
of the tube, bend it gently and do
not bend the tube at a radius
curvature of less than 100 mm.

3. Remove the flare nut from the

unit and be sure to mount it on
the copper tube.

4. Make a flare at the end of copper

tube with a flare tool (Figure 14,15).

Outdoor Unit Installation

1. Install the unit mounting pads

(4 places) into the bottom channels
by tapping gently with a plastic or
rubber tipped hammer.

2. Set the unit on a strong surface

such as one made of concrete to
minimize shock and vibration and
to locate the unit securely.

3. Do not set the unit directly on the

ground.

Connecting the Unit with
Flaring Procedure.

Flaring (If piping is procured or cut at
the site).

1. Cut the copper tube to the

required length with a tube cutter.
It is recommended to cut approx.
30-50 cm. longer than the tubing
length you estimate.

2. Hold each pipe downward when

cutting and remove burrs at the
end of the copper tube with a tube
reamer or file. This process is
important and should be done
carefully to make a good flare
(Figure 12 and Figure 13).

Flare nut

Copper tubing

Flare tool

Figure 14

Figure 15

L

Check if (L) is flared uniform
and is not cracked or scratched.
L Dimension:

1.4 to 1.7 mm (6.35 mm dia)
1.8 to 2.0 mm (9.53 mm dia)
1.9 to 2.2 mm (12.7 mm dia)
2.1 to 2.4 mm (15.88 mm dia)

Figure 12

Copper

tubing Reamer

Figure 13

Deburring

Before

After

6. If the copper tube is bent or pulled

too often, it will become stiff. Do
not bend the pipe more than three
times at one place.

Cautions before Connecting
Tubes Tightly

7. Be sure to apply a sealing cap

or water-proof tape to prevent
dust or water from getting into
the tubes before they are used.

8. Be sure to apply refrigerant

lubricant to the matching
surfaces of the flare and union
before connecting them together.
This is effective for reducing gas
leaks (Figure 16).

Figure 16

Apply refrigerant lubricant here

Figure 17

Union

Flare nut

Connection

9. For proper connection, align the

union tube and flare tube straight
with each other, then screw in the
flare nut lightly at first to obtain a
smooth match (Figure 17).

When reaming, hold the tube end
downward and be sure that no
copper scraps fall into the tube.

10. Tighten the flare nut to the

specified tightening torque with
torque wrench and adjustable
wrench (Figure 18).

11. Repeat the process above for the

remaining line.

Содержание ADAMO MCW 5097BA00

Страница 1: ...ADAMO Installation Manual Split System Wall Type MCW Series 50 Hz MS SVN003 EN January 2003...

Страница 2: ...7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warning Warnings are provided at appropriate...

Страница 3: ...MS SVN003 EN 3 Contents General Information 2 Typical Installation 4 Location and Preparation of Unit 5 Unit Installation 6 Wiring Diagram 12 Dimensional Data 13 Notes 14...

Страница 4: ...rol Air Filter Water Condensated Drain Tube Installation Items The following items are supplied with the indoor unit to provide proper system installation 1 Wall Bracket For indoor unit installation 4...

Страница 5: ...m or flammable gas Do not install the unit where it will be exposed to direct sunlight Outdoor Unit Leave the spacing shown in Figure 3 for required air flow If possible do not install the unit where...

Страница 6: ...center is not aligned condensate leakage can occur If the wall pipe is not used the wiring cable connecting the indoor and outdoor units may become frayed and cause electric current leakage to earth 3...

Страница 7: ...ing and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall bracket 6 Check to insure that Ref Figure 10 The top and bottom hooks are hooked firmly and...

Страница 8: ...s process is important and should be done carefully to make a good flare Figure 12 and Figure 13 Flare nut Copper tubing Flare tool Figure 14 Figure 15 L Check if L is flared uniform and is not cracke...

Страница 9: ...expose the control to the indoor unit s supply air stream 3 Do not place in a confined space 4 Attach the remote control holder as shown in Figure 19 Evacuation and Refrigerant Charge 1 Air Evacuation...

Страница 10: ...e piping before adding refrigerant Add refrigerant through the charging valve after the completion of removing the blanking caps and fully open the service valves Gas Leakage Inspection After charging...

Страница 11: ...rate normally 4 Is the condensate drain normal and freely flowing water Outdoor Unit 5 Is there any abnormal noise and vibration during operation 6 Will noise air flow or drain water from the unit dis...

Страница 12: ...12 MS SVN003 EN Wiring Diagram...

Страница 13: ...NSIONS MM CLEARANCE MM WEIGHT KG A B C D E F MCW 5097BA00 900 00 180 00 265 00 10 00 MCW 5127BA00 900 00 180 00 265 00 100 00 50 00 500 00 10 00 MCW 5187BA00 1 165 00 180 00 310 00 14 00 MCW 5247BA00...

Страница 14: ...14 MS SVN003 EN Notes...

Страница 15: ...MS SVN003 EN 15 Notes...

Страница 16: ...ithout notice Literature Order Number MS SVN003 EN 0103 Supersedes MS SVN003 EN 1200 Stocking Location Bangkok Thailand Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Ba...

Отзывы: