10

MS-SVN003-EN

Figure 22

Pipe length

16ft

23ft

33ft

(5m)

(7m)

(10m)

Additional refrigerant

None 1.1 oz 2.8 oz

(R22)

(32g)

(80g)

5. Reinstall the blanking caps of the

service valves.

6. Disconnect the service hoses and

reinstall the cap on the charging
port. (Tightening torque: 70 to
90 kg

f

 - cm).

2. Additional Charge

Refrigerant suitable for a piping length
of 3.5 to 5.0 meters is charged in the
outdoor unit from the factory. When the
piping is longer than 5 m, additional
charging is necessary. For the
additional amount, see table below.

Outdoor Unit

Figure 20

Refrigerant pipe

Blank cap

Charging port

Cap

Service hose

with valve core

Service valve

Gauge manifold

Vacuum

pump

Service hose

Between 5 m and 10 m, when using
connection pipe lengths other than
that in the table, charge additional
refrigerant with 0.56 oz (16g)/3.3ft.

Caution

• FREON GAS “R22” ONLY

• Always evacuate air from the piping

before adding refrigerant.

• Add refrigerant through the

charging valve after the completion
of removing the blanking caps and
fully open the service valves.

Gas Leakage Inspection

After charging with refrigerant, check
the joints for gas leakage with gas leak
detector or a soap bubble solution.

Figure 21

Outdoor Unit Wiring

1. Remove the outdoor unit terminal

cover (Figure 21).

2. Route the connection cable through

the cable entry brushing and up to
the terminal block.

3. Insert the end of the cable wires

into the terminal block connectors
as shown on the unit wiring
diagram (Figure 11).

4. Tighten the terminal block

connector screws.
(Torque: 7-12 kgf-cm).

• The appliance shall be installed in

accordance with national wiring
regulation.

Caution

• The connector cable wires must be

connected such that terminal
numbers on the indoor unit match
those on the terminal block of the
outdoor unit (Figure 11).

• Insert the connection cable wires

into the terminal block firmly.
Incorrect insertion may cause a
safety problem.

5. Replace the outdoor unit terminal

cover.

Drain hose

Содержание ADAMO MCW 5097BA00

Страница 1: ...ADAMO Installation Manual Split System Wall Type MCW Series 50 Hz MS SVN003 EN January 2003...

Страница 2: ...7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warning Warnings are provided at appropriate...

Страница 3: ...MS SVN003 EN 3 Contents General Information 2 Typical Installation 4 Location and Preparation of Unit 5 Unit Installation 6 Wiring Diagram 12 Dimensional Data 13 Notes 14...

Страница 4: ...rol Air Filter Water Condensated Drain Tube Installation Items The following items are supplied with the indoor unit to provide proper system installation 1 Wall Bracket For indoor unit installation 4...

Страница 5: ...m or flammable gas Do not install the unit where it will be exposed to direct sunlight Outdoor Unit Leave the spacing shown in Figure 3 for required air flow If possible do not install the unit where...

Страница 6: ...center is not aligned condensate leakage can occur If the wall pipe is not used the wiring cable connecting the indoor and outdoor units may become frayed and cause electric current leakage to earth 3...

Страница 7: ...ing and drain hose through the wall hole hang the indoor unit on the hooks at the top and bottom of the wall bracket 6 Check to insure that Ref Figure 10 The top and bottom hooks are hooked firmly and...

Страница 8: ...s process is important and should be done carefully to make a good flare Figure 12 and Figure 13 Flare nut Copper tubing Flare tool Figure 14 Figure 15 L Check if L is flared uniform and is not cracke...

Страница 9: ...expose the control to the indoor unit s supply air stream 3 Do not place in a confined space 4 Attach the remote control holder as shown in Figure 19 Evacuation and Refrigerant Charge 1 Air Evacuation...

Страница 10: ...e piping before adding refrigerant Add refrigerant through the charging valve after the completion of removing the blanking caps and fully open the service valves Gas Leakage Inspection After charging...

Страница 11: ...rate normally 4 Is the condensate drain normal and freely flowing water Outdoor Unit 5 Is there any abnormal noise and vibration during operation 6 Will noise air flow or drain water from the unit dis...

Страница 12: ...12 MS SVN003 EN Wiring Diagram...

Страница 13: ...NSIONS MM CLEARANCE MM WEIGHT KG A B C D E F MCW 5097BA00 900 00 180 00 265 00 10 00 MCW 5127BA00 900 00 180 00 265 00 100 00 50 00 500 00 10 00 MCW 5187BA00 1 165 00 180 00 310 00 14 00 MCW 5247BA00...

Страница 14: ...14 MS SVN003 EN Notes...

Страница 15: ...MS SVN003 EN 15 Notes...

Страница 16: ...ithout notice Literature Order Number MS SVN003 EN 0103 Supersedes MS SVN003 EN 1200 Stocking Location Bangkok Thailand Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Ba...

Отзывы: