10
MS-SVN003-EN
Figure 22
Pipe length
16ft
23ft
33ft
(5m)
(7m)
(10m)
Additional refrigerant
None 1.1 oz 2.8 oz
(R22)
(32g)
(80g)
5. Reinstall the blanking caps of the
service valves.
6. Disconnect the service hoses and
reinstall the cap on the charging
port. (Tightening torque: 70 to
90 kg
f
- cm).
2. Additional Charge
Refrigerant suitable for a piping length
of 3.5 to 5.0 meters is charged in the
outdoor unit from the factory. When the
piping is longer than 5 m, additional
charging is necessary. For the
additional amount, see table below.
Outdoor Unit
Figure 20
Refrigerant pipe
Blank cap
Charging port
Cap
Service hose
with valve core
Service valve
Gauge manifold
Vacuum
pump
Service hose
Between 5 m and 10 m, when using
connection pipe lengths other than
that in the table, charge additional
refrigerant with 0.56 oz (16g)/3.3ft.
Caution
• FREON GAS “R22” ONLY
• Always evacuate air from the piping
before adding refrigerant.
• Add refrigerant through the
charging valve after the completion
of removing the blanking caps and
fully open the service valves.
Gas Leakage Inspection
After charging with refrigerant, check
the joints for gas leakage with gas leak
detector or a soap bubble solution.
Figure 21
Outdoor Unit Wiring
1. Remove the outdoor unit terminal
cover (Figure 21).
2. Route the connection cable through
the cable entry brushing and up to
the terminal block.
3. Insert the end of the cable wires
into the terminal block connectors
as shown on the unit wiring
diagram (Figure 11).
4. Tighten the terminal block
connector screws.
(Torque: 7-12 kgf-cm).
• The appliance shall be installed in
accordance with national wiring
regulation.
Caution
• The connector cable wires must be
connected such that terminal
numbers on the indoor unit match
those on the terminal block of the
outdoor unit (Figure 11).
• Insert the connection cable wires
into the terminal block firmly.
Incorrect insertion may cause a
safety problem.
5. Replace the outdoor unit terminal
cover.
Drain hose