Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines
from outdoor to indoor unit should NOT
exceed sixty (60) feet.
2. The maximum vertical change should not
exceed sixty (60) feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note:
For line lengths greater than sixty (60)
feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revi-
sion).
When mounting the outdoor unit on a roof, be
sure the roof will support the unit’s weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
D
W
H
60’
Max
Vertical
Change
Standard
Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
Unit Dimensions and Weight
Models
H x W x D (in)
Weight* (lb)
A4AC6018A
28.6 X 23.6 X 23.6
130
A4AC6024A
28.6 X 25.6 X 25.6
134
A4AC6030A
28.6 X 29.8 X 29.8
160
A4AC6031A
36.6 X 29.8 X 29.8
184
A4AC6036A
32.6 X 29.8 X 29.8
161
A4AC6037A
36.6 X 34.3 X 34.3
212
A4AC6042A
44.6 X 34.3 X 34.3
252
A4AC6048A
44.6 X 34.3 X 34.3
256
A4AC6060A
44.6 X 34.3 X 34.3
277
* Weight values are estimated.