SSP-PRC001-EN
35
Electrical Data
Unit Wiring with Electric Heat
BAYHTRLW05A
5
1
10
15
BAYHTRLW10A
9.96
1
16
20
BAYHTRLW15A
14.96
TWE120AW
575/3/60
1
22
25
BAYHTRLW25A
24.92
TWE120BW
2
35
35
BAYHTRLW35A
34.88
2
47
50
(i)
kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)2 x Rated Capacity.
(ii)
Any power supply and circuits must be wired and protected in accordance with local codes.
(iii)
The HACR circuit breaker is for U.S.A. installations only.
(iv)
Field wire must be rated at least 75 C.
(v)
Field wire must be rated at least 90 C.
(vi)
With motor field converted to 460V.
Table 38. Unit Wiring with Electric Heat (Single Point Connection) - 15 and 20 Ton Air Handlers
Heater
Model No.
Heater KW
Rating
(i)
(i)
kW ratings are at: 208/240V for 208-230V air handlers.
480V for 460V air handlers
600V for 575V air handlers
For other than rated voltage, capacity = (Voltage/Rated Voltage)
2
x Rated Capacity.
To Use
With Unit
Unit Power
Supply
Control
Stages
Minimum Circuit
Ampacity
(ii)
(ii)
Any power supply and circuits must be wired and protected in accordance with local codes.
Maximum Fuse or
HACR Circuit
Breaker Size
(
ii
)(iii)
(iii)
The HACR circuit breaker is for U.S.A. installations only.
BAYHTRM310A
7.50/10.00
1
38/42
40/45
BAYHTRM320A
14.96/19.92
1
64/72
70/80
BAYHTRM330A
22.50/29.92
TWE180B3
208-230/3/60
2
90/102
90/110
BAYHTRM350A
37.42/49.84
2
142/162
(iv)
(iv)
Field wire must be rated at least 90 C.
150/175
BAYHTRM310A
7.50/10.00
1
45/49
50/50
BAYHTRM320A
14.96/19.92
1
71/79
80/80
BAYHTRM330A
22.50/29.92
TWE240B3, E3
208-230/3/60
2
97/109
100/110
BAYHTRM350A
37.42/49.84
2
144/169
(
iv
)
150/175
BAYHTRM410A
10
1
21
25
BAYHTRM420A
19.92
1
36
40
BAYHTRM430A
29.92
TWE180B4
460/3/60
2
51
60
BAYHTRM450A
49.84
2
81
90
BAYHTRM410A
10
1
24
25
BAYHTRM420A
19.92
1
34
40
BAYHTRM430A
29.92
TWE240B4, E4
460/3/60
2
54
60
BAYHTRM450A
49.84
2
84
90
BAYHTRMW10A
10
1
17
20
BAYHTRMW20A
19.92
1
30
30
BAYHTRMW30A
29.92
TWE180BW
575/3/60
2
42
45
BAYHTRMW50A
49.84
2
67
70
BAYHTRMW10A
10
1
20
25
BAYHTRMW20A
19.92
1
32
35
BAYHTRMW30A
29.92
TWE240BW, EW
575/3/60
2
45
50
BAYHTRMW50A
49.84
2
70
80
Table 37.
Unit Wiring with Electric Heat (Single Point Connection) - 5, 7½ and 10 Ton Air Handlers
Heater Model No.
Maximum Fuse
Heater KW
Rating
(i)
To Use With Unit
Unit Power
Supply
Control Stages
Minimum Circuit
Ampacity
(ii)
Maximum Fuse or
HACR Circuit
Breaker Size
(
ii
)
,
(iii)
Содержание 5-20 Tons
Страница 7: ...SSP PRC001 EN 7 Application Considerations Figure 7 Typical Vertical Air Handler Application...
Страница 42: ...42 SSP PRC001 EN Figure 20 7 Tons TWA090 Heat Pump All dimensions are in inches Dimensional Data...
Страница 43: ...SSP PRC001 EN 43 Dimensional Data Figure 21 10 Tons TWA120A Heat Pump All dimensions are in inches 10 Tons...
Страница 44: ...44 SSP PRC001 EN Dimensional Data 15 Tons Figure 22 15 Tons TWA180B Heat Pump All dimensions are in inches...
Страница 45: ...SSP PRC001 EN 45 Dimensional Data 20 Tons Figure 23 20 Tons TWA240B Heat Pump All dimensions are in inches...
Страница 49: ...SSP PRC001 EN 49 Dimensional Data 15 Tons Figure 27 15 Tons TWE180 Air Handlers All dimensions are in inches...
Страница 51: ...SSP PRC001 EN 51 Dimensional Data 20 Tons Figure 30 20 Tons TWE240B Air Handlers...
Страница 57: ...SSP PRC001 EN 57 Dimensional Data Accessories Spring Isolators Figure 39 5 20 Ton Spring Isolators...
Страница 63: ......