30
SSP-PRC001-EN
Performance Data
5-20 Tons Static Pressure Drop, Auxiliary Heat Capacity
Table 31. Static Pressure Drop Through Accessories (inches of water column)
(i)
- Air Handlers
(i)
Return air filter ESP included in Fan Performance Table data.
Tons
Unit Model No.
CFM
Return
Grille
Discharge
Plenum and
Grille
(ii)
(ii)
At louver opening angle of 42 degrees. For ESP at other angle openings, see accessory Installer’s Guide.
Electric Heaters (kW)
Hydronic Coils
5-10
15-20
25-30
35-50
Steam
Hot Water
5
1600
0.12
0.21
0.08
0.08
0.14
-
.44
.31
TWE060A
2000
0.18
0.33
0.13
0.13
0.19
-
.62
.44
TWE060B
2400
0.28
0.47
0.19
0.19
0.37
-
.80
.59
7½
2400
0.08
0.27
0.03
0.06
0.08
0.12
.38
.23
TWE090A
3000
0.13
0.4
0.06
0.12
0.17
0.23
.50
.33
TWE090B
3600
0.18
0.58
0.08
0.16
0.24
0.32
.66
.44
10
3200
0.07
0.43
0.06
0.13
0.19
0.26
.42
.40
TWE120A
4000
0.11
0.66
0.10
0.20
0.30
0.40
.59
.56
TWE120B
4800
0.15
0.95
0.14
0.28
0.42
0.57
.76
.75
15
4800
0.09
0.23
0.03
0.03
0.06
0.08
.46
.38
TWE180B
6000
0.15
0.34
0.06
0.06
0.12
0.17
.64
.54
7200
0.2
0.49
0.08
0.08
0.16
0.24
.82
.72
6400
0.11
0.43
0.06
0.06
0.13
0.19
.50
.41
20
TWE240B/TWE240E 8000
0.17
0.66
0.10
0.10
0.20
0.30
.70
.58
9600
0.23
0.95
0.14
0.14
0.28
0.42
.89
.78
Table 32. Auxiliary Electric Heat Capacity - Air Handler
Stage 1
Stage 2
Total
Unit Model No.
Total
kW
No. of
Stages
kW Input
BTUH
Output
kW Input
BTUH
Output
kW Input
BTUH
Output
5.00
1
5.00
17,065
-
-
5.00
17,065
TWE060A3, A4, AW
9.96
1
9.96
33,993
-
-
9.96
33,993
TWE060B3, B4
14.96
1
14.96
51,058
-
-
14.96
51,058
24.92
2
14.96
51,058
9.96
33,993
24.92
85,051
5.00
1
5.00
17,065
-
-
5.00
17,065
TWE090,120A3,AW
9.96
1
9.96
33,993
-
-
9.96
33,993
TWE090B3
14.96
1
14.96
51,058
-
-
14.96
51,058
TWE120B3, BW
24.92
2
14.96
51,058
9.96
33,993
24.92
85,051
TWE060,090,120A1
5.76
1
5.76
19,659
-
-
5.76
19,659
TWE060B1
11.52
1
11.52
39,318
-
-
11.52
39,318
TWE090B1
17.28
1
17.28
58,977
-
-
17.28
58,977
TWE120B1 23.04
2
11.52
39,318
11.52
39,318
23.04
78,636
TWE090,120A1
28.8
2
17.28
58,977
11.52
39,318
28.8
98,295
TWE120B1
TWE090,120A3, AW
34.88
2
19.92
67,987
14.96
51,058
34.88
119,045
TWE120B3, BW
10.00
1
10.00
34,130
-
-
10.00
34,130
19.92
1
19.92
67,987
-
-
19.92
67,987
TWE180, 240B, 240E
29.92
2
19.92
67,987
10.00
34,130
29.92
102,117
49.84
2
29.92
102,117
19.92
67,987
49.84
170,104
Notes:
Heaters are rated at 240V, 480V and 600V. For other than rated voltage capacity = (Voltage/Related Voltage)
2
x Rated Capacity.
Содержание 5-20 Tons
Страница 7: ...SSP PRC001 EN 7 Application Considerations Figure 7 Typical Vertical Air Handler Application...
Страница 42: ...42 SSP PRC001 EN Figure 20 7 Tons TWA090 Heat Pump All dimensions are in inches Dimensional Data...
Страница 43: ...SSP PRC001 EN 43 Dimensional Data Figure 21 10 Tons TWA120A Heat Pump All dimensions are in inches 10 Tons...
Страница 44: ...44 SSP PRC001 EN Dimensional Data 15 Tons Figure 22 15 Tons TWA180B Heat Pump All dimensions are in inches...
Страница 45: ...SSP PRC001 EN 45 Dimensional Data 20 Tons Figure 23 20 Tons TWA240B Heat Pump All dimensions are in inches...
Страница 49: ...SSP PRC001 EN 49 Dimensional Data 15 Tons Figure 27 15 Tons TWE180 Air Handlers All dimensions are in inches...
Страница 51: ...SSP PRC001 EN 51 Dimensional Data 20 Tons Figure 30 20 Tons TWE240B Air Handlers...
Страница 57: ...SSP PRC001 EN 57 Dimensional Data Accessories Spring Isolators Figure 39 5 20 Ton Spring Isolators...
Страница 63: ......