background image

Page 22 

                 

Installer’s Guide

  Does the unit run and operate as described in the section on 

Sequence of Operation in response to the room thermostat?

 Are the condenser fan and indoor blower operating correctly  

  with proper rotation and without undue noise?

 Is the compressor operating correctly and has the system been  

  checked with a charging chart?

 Has the voltage and running current been checked to deter 

  mine if it is within limits?

 Has the thermostat been checked for calibration and the air    

discharge grilles adjusted to balance the system?

 Has the ductwork been checked for air leaks and 

 condensation?

 Has the furnace manifold pressure been checked and 

  adjusted if necessary?

 Has the heating air temperature rise been checked?

 Has the unit been checked for tubing and sheet metal rattles?   

  Are there any other unusual noises to be checked?

 Are all covers and panels in place and properly fastened?

 Has the owner been instructed on the proper operation and 

  maintenance of the unit? Be sure to leave this manual with the  
 owner.

Final Installation Checklist

Starting the Unit in the Cooling Mode

To start the unit in the cooling mode, set the thermostat system switch 
to COOL and move the thermostat COOL indicator to a setting below 
room temperature.  The condenser (outdoor) fan motor compressor 
and evaporator (indoor) fan motor will operate automatically.

NOTE:

  See the section on “Sequence of Operation” for a de-

scription of the cooling operating sequence.

Operating Pressures

After the unit has operated in the cooling mode for a short period of 
time, install pressure gauges on the gauge ports of the discharge 
and suction line valves.  Check the suction and discharge pressures 
and compare them to the normal operating pressures provided in 
the unit’s 

SERVICE FACTS.

 

NOTE:

 Do not use the PRESSURE CURVES from the unit's 

SERVICE FACTS to determine the unit refrigerant charge. The 
correct charge is shown on the unit nameplate. To charge the 
system accurately, weigh in the charge according to the unit 
nameplate and check subcooling against the Subcooling Charg-
ing Table in the SERVICE FACTS.

Voltage

With the compressor operating, check the line voltage at the unit.  
The voltage should be within the range shown on the unit name-
plate.  If low voltage is encountered, check the size and length of 
the supply line from the main disconnect to the unit.  The line may 
be undersized for the length of the run.

Cooling Shut Down

Set the system mode to OFF or adjust the cooling setpoint to above 
room temperature.

Heating Cycle

These units are equipped with a solid-state ignition control that lights 
the burners each time the thermostat calls for heat.  The burners 
are extinguished during the OFF cycle.

The gas heating section of the unit can be started using the follow-
ing procedure:

  1. Be sure the thermostat is at its lowest setting and the power to 

the unit is off.

 

a. Turn the main shutoff valve on the gas supply line ON.

 

b.  Turn or switch the manual valve on the combination gas valve 

ON position.

  2. Be sure the burner compartment access panel is in place.
 

a. Turn on the electrical power to the unit.

 

b.  Turn the thermostat to the highest setting in the heating cycle. 

 

  3. As the thermostat calls for heat, the system cycles as follows:
 

a. The combustion blower is energized.

 

b. The pressure switch is closed.

 

c.  The gas valve opens and the ignitor lights the burner.

 

d. Cycle the thermostat on and off a few times to check out the 

control system and burner operation characteristics.

  4. With the burners operating, check the manifold pressure with 

a manometer.  Do not exceed recommended pressures.

  5.  Adjust the unit to obtain an air temperature rise within the range 

that is specified on the unit nameplate.

  

NOTE

:  For manifold pressures and orifice sizes for gas with 

other BTU ratings, contact the local gas utility.  Manifold pressure 
should be 1.8  (low) to 3.5 (high)  inches water column  (+0.1).  
Input must 

not

 exceed the value shown on the unit nameplate.

  6.  Set the heat anticipator of the thermostat to equal the amperage 

draw of the gas valve, approximately 0.7.

  7. Set the thermostat at the desired temperature setting and the 

unit will function automatically.

Starting the Unit in the Gas Heating Mode

  1. Check to make sure all grilles and registers are open and all 

unit access doors are closed before start-up.

  2. Purge the gas supply line of air by opening the union ahead of 

the unit.  When the odor of gas is detected, retighten the union 
and wait five (5) minutes before proceeding.

  3. Set the wall thermostat to its lowest position and place the fan 

switch in the AUTO or ON position.

  4. Open the main gas valve(s) and turn on the unit power supply.

  5. Reset the heating temperature lever on the room thermostat 

at the highest value above room temperature. The combustion 
blower motor should energize. The main burners should light 
within 20-25 seconds. Initial start may be delayed somewhat if 
the unit has not been purged and air is trapped in the gas line.

   NOTE:

  Blue smoke produced by the heat exchanger during the 

initial burner firing is caused by a thin film of oil on the surface 
of the heat exchanger. This oil will burn off quickly.

Содержание 4YCZ6024

Страница 1: ...ures on the fan Operating the unit without the access panels properly installed may result in severe personal injury or death WARNING SAFETY HAZARD This information is for use by individuals having adequate backgrounds of electrical and mechanical experience Any attempttorepairacentralairconditioningproductmayresult inpersonalinjuryand orpropertydamage Themanufacturer or seller cannot be responsib...

Страница 2: ...R 410A operating pressure exceeds the limit of R 22 Proper service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and approved POE compres sor oil IMPORTANT Wear appropriate gloves arm sleeve protectors and eye protection when servicing or maintaining this equipment PRECAUTIONARY MEASURES Avoid breathi...

Страница 3: ...g 16 Gas Piping Installation 16 Pipe Delivery Schedule natural gas only 17 Gas Pressure Set up Precautions 17 Gas Supply Line Pressure all fuels 17 Verify Manifold Pressure 18 Input Check and Adjustment 18 High Altitude Installation 19 Air Filter Installation 19 Electrical Wiring 19 Electrical Connections 18 Electrical Power 19 Disconnect Switch 19 Over current Protection 19 Power Wiring 19 Contro...

Страница 4: ... Determine Unit Clearances Figure 1 4YCZ6024 6036 1 of 3 Figures 1 through 6 show the unit critical dimensions DWG NO D673947G01_REVC NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit ...

Страница 5: ...Page 5 Installer s Guide Figure 2 4YCZ6024 6036 2 of 3 ...

Страница 6: ...uide Step 2 Determine Unit Clearances Figure 1 4YCZ6024 6036 3 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit ...

Страница 7: ...Page 7 Installer s Guide Figure 4 4YCZ6048 through 4YCZ6060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit ...

Страница 8: ...Page 8 Installer s Guide Figure 5 4YCZ6048 through 4YCZ6060 2 of 3 ...

Страница 9: ...Page 9 Installer s Guide Figure 6 4YCZ6048 through 4YCZ6060 3 of 3 ...

Страница 10: ...r to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabricated curb should be in place before the unit is hoisted to the roof top The Roof Mounting Curb frame must be installed on a flat level section of the roof maximum of 1 4 per foot pitch and provide a lev...

Страница 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflow Perform this procedure to convert the unit to down airflow 1 Remove the three 3 sheet metal screws securing the supply aircover and the four 4 sheet metal screws securing the return air cover from t...

Страница 12: ...tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparing the unit for lifting check the unit dimension drawings for center of gravity for lifting safety Figures 1 to 6 page 4 9 Because of placement of internal components the unit s weight may be unevenly distributed Approximate unit weights are also provided in the unit drawings NOTE When unit rigging and...

Страница 13: ... roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails are required One on each end to support the edges of the unit and one across the center of the unit The center rail must run inside both drip lips Vibration isolators should be installed as indicated on...

Страница 14: ...sible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars Base of unit rest on top of curb rails Drip lip on perimeter of unit Top shipping skid attached to unit IMPORTANT To prevent damage to the sides and top of the unit when hoisting retain the top shipping skid on the unit or use spreader bars...

Страница 15: ...orizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Angle Iron Frame Roof Flashing Supply Air Channel Iron Center Support Center Support required on all Frame Applications ...

Страница 16: ...oise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two 2 feet from the unit to minimize noise and resistance To prevent leaking do not attach the ductwork to the bottom of the unit base refer to the bottom example in Figure 14 A 3 4 inch female NPT cond...

Страница 17: ...e making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local codes the installation must con form with American National Standard Z223 1 National Fuel Gas Code Latest Revision The available gas supply must agree with the required gas supply marked on the unit nam...

Страница 18: ...nchonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the pipe opening should be closed with the filler barrier plug provided Manifold Pressure Check the manifold pressure at the unit gas valve Do not exceed the recommended pressure shown on the unit namepl...

Страница 19: ...hat require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8 WC Low Fire Natural Gas heating value of 950 btu cuft Electrical Power It is important that proper electrical power be available for the unit Voltage variation should remain within the limits found on the uni...

Страница 20: ...itioning systems been checked at the service ports for charge and leak tested if necessary Does the condenser fan and indoor blower turn free without rub bing and are they tight on the shafts Has the indoor blower speed been determined and the proper speed been set See the Unit Wiring Diagram Has all work been done in accordance with applicable local and national codes Are all covers and access pa...

Страница 21: ...Page 21 Installer s Guide Figure 22 4YCZ6 Field Wiring Diagram NOTE For economizer wiring instructions see the Installer s Guide that came with your economizer ...

Страница 22: ...cooling setpoint to above room temperature Heating Cycle Theseunitsareequippedwithasolid stateignitioncontrolthatlights the burners each time the thermostat calls for heat The burners are extinguished during the OFF cycle The gas heating section of the unit can be started using the follow ing procedure 1 Be sure the thermostat is at its lowest setting and the power to the unit is off a Turn the ma...

Страница 23: ...ond postpurge The indoor blower motor will continue to operate at the current speed for 60 or 90 seconds after the flames are extinguished Sequence of Operation Safety Sequences This product is equipped with safety devices to protect against abnormal conditions The temperature limit switch TCO is located on the blower barrier andcanbeaccessedthroughtheblowercompartment Thisautomatic reset device p...

Страница 24: ... damage Do not store combustible materials gasoline or other flammable vapors or liquids near the unit WARNING Someoftheperiodicmaintenancefunctionsofthe4YCZ6unitcan beperformedbytheowner thisincludesreplacingthedisposable or cleaning the permanent air filters cleaning the unit cabinet and conducting a general unit inspection on a regular basis Filters When the system is in constant operation insp...

Страница 25: ... Hood and Combustion Blower Cleaning Manifold Pressure Check and Adjust 1 Connect a manometer to the pressure tap at the outlet side of the unit s gas valve remove the Control Heat access panel Read the manifold pressure with the burners firing See Figure 16 on page 17 for gas valve connections 2 If the manifold pressure reading does not match the value indicated on the unit s nameplate the unit s...

Страница 26: ... 3 Flashes Pressure switch problem detected Fast Flash Rate Not used 4 Flashes High Limit switch protection device open Steady ON Normal No Call for Heat 5 Flashes Flame sensed and gas valve not energized or flame sensed and no W signal 6 Flashes Flame Rollout Switch open 7 Flashes Thermostat miswired W1 W2 Fast Flash Rate The LED will flash on for 1 4 second and off for 1 4 second Slow Flash Rate...

Страница 27: ...Page 27 Installer s Guide ...

Страница 28: ...uide Trane 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specification without notice 2017 Trane 09 18 ...

Отзывы: