background image

 

                                                                 

  Page 15

Installer’s Guide

FLASH RATE INDICATIONS:

1 — Flash/Second 

=  Normal operation.

2 — Flashes/Second  

=  Fault A (Low DT) i.e.: Inoperative compres-

sor, loss of charge, open ambient sensor, 
shorted coil sensor.

3 — Flashes/Second 

=  Fault B (20 defrosts terminated on time)

 

  Fault C (High DT) i.e.: SOV stuck in heating, 

shorted ambient sensor, open coil sensor, 
closed TXV,OD motor failure, OD fan on in 
defrost, undercharged unit.

4 — Flashes/Second  

=  Fault A & C or A & B

For additional information consult Pub. No. 34-1005-03 Heat Pump 
Defrost Controls.

PROCEDURE FOR TESTING SENSORS

Measure the temperature the subject sensor is exposed to.  If the sensor is 
mounted on a tube, place the lead on an Annie A-8 (or equiv.) temperature 
tester on the same tube near the sensor and insulate the bulb.

Unplug the sensor and measure the resistance with a good quality ohmmeter 
(Simpson 260 or equiv.).  Read the value as quickly as possible to prevent 
the meter current from changing the resistance reading.

Using the chart on the right, locate (as close as possible) the actual sensor 
temperature.  The measured resistance should be relatively close to the 
resistance value shown in the chart.

Example:

 

Sensor temp. 

= 19°F.

 

Measured Resistance = 46K ohms

This sensor is good since the measured value is relatively close to the chart 
value.

DEFROST CONTROL

The demand defrost control measures heat pump outdoor ambient temperature with 

a sensor located outside the outdoor coil.  A second sensor located on the outdoor 

coil is used to measure the coil temperature.  The difference between the ambient 

and the colder coil temperature is the difference or delta-T measurement.  This 

delta-T measurement is representative of the operating state and relative capacity 

of the heat pump system.  By measuring the change in delta-T, we can determine 

the need for defrost.  The coil sensor also serves to sense outdoor coil temperature 

for termination of the defrost cycle.

FAULT DETECTION

A fault condition is indicated by the flashing light on the defrost control inside the 

heat pump control box.

In normal operation, the defrost control light will flash once each second. If the light 

is flashing more than once per second or not-at-all, refer to the service manual for 

that unit.

PIN   IDENTIFICATION (See Figure) 

1.   TEST_COMMON (Shorting any of  the other pins to this pin causes  the func-

tion of the other pin to be executed. Leaving this pin open results in the normal 
mode of operation.) 

2.  TST   =   Test  (Shorting TEST_COMMON  to this pin speeds up all defrost 

board timings.)

3.  FRC_DFT  =  Forced Defrost  (Short TEST_COMMON to this pin for two (2) 

seconds to initiate a forced defrost. Remove the short after defrost initiates.)

DEFROST CONTROL CHECKOUT

Normal operation requires:

a.  LED on board flashing 1 time/second.

b.  24V AC between R & B

c.  24V AC between Y & B with unit operating

d. Defrost initiation when FRC_DFT pin is shorted to  TEST_COMMON pin.

If a defrost control problem is suspected, proceed to DEMAND DEFROST CON-

TROL CHECKOUT in this Service Facts.

Figure 8. Pin Identification

FRC_DFT

TEST_COMMON

TST

Do NOT connect 24 VAC to T1 (ODS-A) terminal. ODS-A thermistor WILL 
BE BLOWN.

WARNING

!

TEMP (ºF)

RESISTANCE

86

7.85K

81

8.85K

75

 10.24K

70

11.59K

65

13.14K

59

15.32K

55

16.93K

50

 19.41K

45

 22.20K

41

24.76K

36

28.45K

32

31.84K

25

37.50K

19

46.44K

14

53.94K

10

57.64K

5

67.06K

0

78.05K

Содержание 4WHC3024

Страница 1: ...C3 IG 4 WARNING HAZARDOUS VOLTAGE DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING 2011 Trane ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES Important This D...

Страница 2: ...evere personal injury or death WARNING IMPORTANT Wear appropriate gloves arm sleeve protectors and eye protection when servicing or maintaining this equipment IMPORTANT Reconnectallgroundingdevices Al...

Страница 3: ...the refrigerant charge has been retained during shipment using the 1 4 flare pressure taps located near the blower panel on the side of the unit NOTE If practical install any internal accessories to...

Страница 4: ...Page 4 Installer s Guide Step 2 Determine Unit Clearances Figures 1 and 2 show the unit critical dimensions Figure 1 4WHC3024 4WHC3042...

Страница 5: ...Page 5 Installer s Guide Figure 2 4WHC3048 4WHC3060...

Страница 6: ...two 2 inches of insulation and weatherproof There must be a weather proof seal where the duct enters the structure 5 Do not expose the unit to direct roof water runoff 6 Seal all holes through exteri...

Страница 7: ...sulation and then weatherproof There must be a weatherproof seal where the duct enters the structure 9 The unit should not be exposed to direct roof water runoff 10 Flexible duct connectors must be of...

Страница 8: ...Page 8 Installer s Guide Figure 3 Ground Level Application DISCHARGE AIR Figure 4 Typical Rooftop Frame Application DISCHARGE AIR...

Страница 9: ...to a closed drain system unless the trap is properly vented Figure 5 Typical Condensate Drain Piping Table 1 Determine Filter Size Filters must be installed in the return air system The above square...

Страница 10: ...in the same conduit with the power wiringunlessClassIwireofthepropervoltageratingisused Routethethermostat cable or equivalent single leads of No 18 AWG colored wire from the thermostat subbase termin...

Страница 11: ...ermostat system switch to COOL Move the thermostat COOL indicator to a setting below room temperature The outdoor fan motor compressor and evaporator fan motor will operate automatically Operating Pre...

Страница 12: ...starts the indoor fan motor Supplementary Heat The supplementary electric heat is brought on when the indoor temperature drops 1 1 2 degrees below the thermostat setting TSH 2 contacts close provid i...

Страница 13: ...Page 13 Installer s Guide Figure 7 Field Hookup Diagram With Supplementary Heaters Dwg No D757386...

Страница 14: ...n safety controls for mechanical cleaning electrical components and wiring for possible replacement and con nection tightness condensate drain for proper sealing and cleaning unit duct connections to...

Страница 15: ...coil temperature is the difference or delta T measurement This delta T measurement is representative of the operating state and relative capacity of the heat pump system By measuring the change in de...

Страница 16: ...k 3 3 Check sensors for correct mounting connection and resistance Remount or replace sensor if necessary 4 Short FRC_DFT pin to TEST_COMMON pin Is defrost cycle initiated N Replace defrost control Y...

Страница 17: ...t control 10 No SOV delay on defrost termination Has J1 been cut Y The soft switch time is defeated when J1 is cut N Replace defrost control 11 ODS A burned out 1 B to T greater than 10 volts Y Check...

Страница 18: ...nstallation operation and maintenance instructions provided by Company with each Product Failure to conform to such specifications and or instructions shall void this limited warranty Company may requ...

Страница 19: ...arranty Periods for certain Products will be extended as stated below Registered Limited Warranty Period SINGLE PHASE R410 OUTDOOR UNITS Base Limited Warranty Period Compressor Outdoor Coil Parts five...

Страница 20: ...ments to record the following information to ensure your product registration process is quick and easy Packaged Unit Serial Number_____________________________________________________ Packaged Unit M...

Отзывы: