background image

Page 14    

                                                              

Installer’s Guide

Owner Maintenance

Some of the periodic maintenance functions of the packaged unit can be 
performed by the owner; this includes replacing the disposable or cleaning the 
permanent air filters, cleaning the unit cabinet, cleaning the condenser coil, and 
conducting a general unit inspection on a regular basis.

Filters
When the system is in constant operation, inspect the filters at least once 
each month.
If the unit has disposable-type filters, replace them with new filters of the same 
type and size. Do not attempt to clean disposable filters.
Permanent-type filters can be cleaned by washing them with a mild detergent 
and water. Make sure that the filters are thoroughly dry before reinstalling them 
in the unit (or duct system).

Note:  It may be necessary to replace permanent filters annually if 
washing fails to clean the filter or if the filter shows signs of dete-
rioration.  Be sure to use the same type and size as was originally 
installed.

Condenser Coil
Be sure to keep all vegetation and debris away from the condenser coil area.

Maintenance

Service Maintenance 

Cooling Season
To keep the unit operating safely and efficiently, the manufacturer recommends 
that a qualified service technician check the entire system at least once each 
season or sooner if needed. The service technician should examine these 
areas of the packaged unit:

  

filters (for cleaning or replacement)

  

motors and drive system components (for proper operation)

  

safety controls (for mechanical cleaning)

  

electrical components and wiring (for possible replacement and con-

nection tightness)

  

condensate drain (for proper sealing and cleaning)

  

unit duct connections (to see that they are physically sound and sealed 

to the unit casing)

  

the unit (for obvious unit deterioration)

Heating Season

  

Complete the following unit inspections and service routines at the 

beginning of each heating season.

  

Visually inspect the unit to ensure that the airflow required for  

combustion and condenser coil is not obstructed from the unit.

  

Inspect the control panel wiring to verify that all electrical connections 

are tight and that the wire insulation is intact.

Final Installation Checklist

  

Does the unit run and operatioe as described in the section on Se-

quence of Operation, page ?, in response to the room thermostat?

  

Are the condenser fan and indoor blower operating correctly with 

proper rotation and without undue noise?

  

Is the compressor operating correctly asnd has the system been 

checked with a charging chart?

  

Has the voltage and running current been checked to determine if it is 

with in limits?

  

Has the thermostat been checked for calibration and the air discharge 

grills adjusted to balance the system?

  

Has the duct work been checked for air leaks and condensation?

  

Has the heating air temperature rise been checked?

  

Has the unit been checked for tubing and sheet metal rattles? Are 

there any other unusual noises to be checked?

  

Are all covers and panels in place and properly fastened?

  

Has the owner been instructed on the proper operation and mainte-

nance of the unit? Be sure to leave this manual with the owner.

Содержание 4WHC3024

Страница 1: ...C3 IG 4 WARNING HAZARDOUS VOLTAGE DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING 2011 Trane ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES Important This D...

Страница 2: ...evere personal injury or death WARNING IMPORTANT Wear appropriate gloves arm sleeve protectors and eye protection when servicing or maintaining this equipment IMPORTANT Reconnectallgroundingdevices Al...

Страница 3: ...the refrigerant charge has been retained during shipment using the 1 4 flare pressure taps located near the blower panel on the side of the unit NOTE If practical install any internal accessories to...

Страница 4: ...Page 4 Installer s Guide Step 2 Determine Unit Clearances Figures 1 and 2 show the unit critical dimensions Figure 1 4WHC3024 4WHC3042...

Страница 5: ...Page 5 Installer s Guide Figure 2 4WHC3048 4WHC3060...

Страница 6: ...two 2 inches of insulation and weatherproof There must be a weather proof seal where the duct enters the structure 5 Do not expose the unit to direct roof water runoff 6 Seal all holes through exteri...

Страница 7: ...sulation and then weatherproof There must be a weatherproof seal where the duct enters the structure 9 The unit should not be exposed to direct roof water runoff 10 Flexible duct connectors must be of...

Страница 8: ...Page 8 Installer s Guide Figure 3 Ground Level Application DISCHARGE AIR Figure 4 Typical Rooftop Frame Application DISCHARGE AIR...

Страница 9: ...to a closed drain system unless the trap is properly vented Figure 5 Typical Condensate Drain Piping Table 1 Determine Filter Size Filters must be installed in the return air system The above square...

Страница 10: ...in the same conduit with the power wiringunlessClassIwireofthepropervoltageratingisused Routethethermostat cable or equivalent single leads of No 18 AWG colored wire from the thermostat subbase termin...

Страница 11: ...ermostat system switch to COOL Move the thermostat COOL indicator to a setting below room temperature The outdoor fan motor compressor and evaporator fan motor will operate automatically Operating Pre...

Страница 12: ...starts the indoor fan motor Supplementary Heat The supplementary electric heat is brought on when the indoor temperature drops 1 1 2 degrees below the thermostat setting TSH 2 contacts close provid i...

Страница 13: ...Page 13 Installer s Guide Figure 7 Field Hookup Diagram With Supplementary Heaters Dwg No D757386...

Страница 14: ...n safety controls for mechanical cleaning electrical components and wiring for possible replacement and con nection tightness condensate drain for proper sealing and cleaning unit duct connections to...

Страница 15: ...coil temperature is the difference or delta T measurement This delta T measurement is representative of the operating state and relative capacity of the heat pump system By measuring the change in de...

Страница 16: ...k 3 3 Check sensors for correct mounting connection and resistance Remount or replace sensor if necessary 4 Short FRC_DFT pin to TEST_COMMON pin Is defrost cycle initiated N Replace defrost control Y...

Страница 17: ...t control 10 No SOV delay on defrost termination Has J1 been cut Y The soft switch time is defeated when J1 is cut N Replace defrost control 11 ODS A burned out 1 B to T greater than 10 volts Y Check...

Страница 18: ...nstallation operation and maintenance instructions provided by Company with each Product Failure to conform to such specifications and or instructions shall void this limited warranty Company may requ...

Страница 19: ...arranty Periods for certain Products will be extended as stated below Registered Limited Warranty Period SINGLE PHASE R410 OUTDOOR UNITS Base Limited Warranty Period Compressor Outdoor Coil Parts five...

Страница 20: ...ments to record the following information to ensure your product registration process is quick and easy Packaged Unit Serial Number_____________________________________________________ Packaged Unit M...

Отзывы: