background image

 18-AD25D1-4C-EN

Installer’s Guide

PAINTED AREAS OF THE UNIT MUST BE SHIELDED 

DURING BRAZING.

4.  Flow a small amount of nitrogen through the tubing    

while brazing.

5.  Use good  brazing technique to make leakproof 

joints.

6.  Minimize the use of sharp 90 degree bends.

7.  Insulate the suction line and its fittings.

8.  Do NOT allow un-insulated lines to come into contact 

with each other.

NOTE:

Torque specification for TXV equals 1/6 turn past finger 

tight. Make sure to backwrench when tightening as 

shown in Firgure 3.

F.  LEAK CHECK

1.  Using a manifold gauge, connect an external supply  

of dry nitrogen to the gauge port on the liquid line.  

2.  Pressurize the connecting lines and indoor coil to 

150  PSIG maximum.

3.  Leak check brazed line connections using soap 

bubbles.  Repair leaks (if any) after relieving 

pressure.

4.  Evacuate and charge the system per the instructions 

packaged with the outdoor unit.

G.  CONDENSATE DRAIN PIPING 

    (SEE FIGURE 5)

NOTE:

When coils are installed above ceilings or in other 

locations  where  damage  from  condensate  overflow 

may occur. A field fabricated auxiliary drain pan shall be 

installed  under the coil enclosure.  Drain lines from this 

pan must be installed, but should NOT be connected to 

the primary drain.

Condensate drain connections are located in the drain pan 

at the bottom of the coil/enclosure assembly.  The female 

threaded  fitting  protrudes  outside  of  the  enclosure  for 

external connection.  A field fabricated trap is not required 

for proper drainage due to the positive pressure of the 

furnace; however, it is  recommended to prevent efficiency 

loss of conditioned air. 
1.  The drain hole in the drain pan must be cleared of all 

insulation.

2.  Insulate the primary drain line to prevent sweating 

where dew point temperatures may be met.  

(Optional depending on climate and application 

needs).

FIELD FABRICATED TRAP

2" MIN.

2" MIN.

CAP OR PLUG

Trap must be within 4' 

of furnace / air handler 

condensate drain connection.

Close as possible

When replacing the bulb and hose clamp, the clamp 

should be "snug" but not "tight" -  spec is to torque the 

hose clamp to 20+/-5in-lb. 

 H.  SECONDARY CONDENSATE DRAIN

A secondary condensate drain connection, now called for 

by many building codes, has been provided, on 4TXFH 

coils.  Reducing fittings and copper tubing can be used in 

most cases.

IMPORTANT:

Plug all drain line connection(s) not used. Do NOT use 

heat or torch near drain fittings.

I.   DUCT CONNECTIONS

The supply and return air duct should be connected to 

the  unit  with  a  flame  retardant  duct  connectors.    Duct 

flange  connections  are  provided  at  both  supply  and 

discharge openings of the coil.

1.  Remove both sealing rubber plugs from the indoor 

coil.

2.  Field supplied tubing should be cut square, round 

and free of burrs at the connecting end.  Clean the 

tubing to prevent contaminants from entering the 

system.

3.  Run the refrigerant tubing into the stub tube sockets 

of the indoor unit coil.

Отзывы: