Pressure Curves
Figure 4. 3.0 Ton Models
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSURE IN LEFT
COLUMN (4).
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
ACTUAL:
(4) DISCHARGE PRESSURE @ 1250 CFM IS 316 PSIG.
DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 1250 CFM IS 142 PSIG.
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
INTERCONNECTING LINES
GAS - 7/8" O.D.
LIQUID - 3/8" O.D.
DWG.NO. 4TWL6036A1
110
115
120
125
130
135
140
145
150
155
160
165
170
40
60
80
100
120
200
250
300
350
400
450
500
550
40
60
80
100
120
(1)
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
30
40
50
60
70
80
90
100
110
120
130
140
-5
5
15
25
35
45
55
65
200
250
300
350
400
450
500
-5
5
15
25
35
45
55
65
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
80, 70, AND 60 DEG F.
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
80, 70, AND 60 DEG F.
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
OUTDOOR TEMPERATURE (Degree F)
OUTDOOR TEMPERATURE (Degree F)
TEM4ATDR
TEM4ATDR
Cooling @ 1250 SCFM
Heating @ 1250 SCFM
D
IS
C
H
A
R
G
E
P
R
E
S
S
U
R
E
(
P
S
IG
)
S
U
C
T
IO
N
P
R
E
S
S
U
R
E
(
P
S
IG
)
Содержание 4TWL6036A1000A
Страница 4: ...4 4TWL6036A SF 1F EN Wiring Figure 1 2 0 3 0 3 5 Ton Models d159503p02...
Страница 5: ...4TWL6036A SF 1F EN 5 Figure 2 2 0 3 0 3 5 Ton Models W Wi ir ri in ng g...
Страница 6: ...6 4TWL6036A SF 1F EN Refrigerant Circuit Diagrams Figure 3 3 0 and 3 5 Ton Models Dwg D158717_RevB...
Страница 19: ...4TWL6036A SF 1F EN 19 Troubleshooting Does a resistance check show an open circuit between R and S...