4TWL6036A-SF-1F-EN
3
Product Specifications
OUTDOOR UNIT
(a) (b)
4TWL6036A1XXXA
POWER CONNS. – V/PH/HZ
(c)
208–230/1/60
MIN. BRCH. CIR. AMPACITY
19
BR. CIR. PROT. RTG. – MAX. (AMPS)
30
COMPRESSOR
CLIMATUFF®- SCROLL
NO. USED – NO. STAGES
1 – 1
VOLTS/PH/HZ
208–230/1/60
R.L. AMPS
(d)
– L.R. AMPS
14.7 – 75
FACTORY INSTALLED
START COMPONENTS
(e)
NO (USE BAYSKT263)
INSULATION/SOUND BLANKET
NO
SUMP HEAT
NO
OUTDOOR FAN
PROPELLER
DIA. (IN.) – NO. USED
27.5 – 1
TYPE DRIVE — NO. SPEEDS
DIRECT – 1
CFM @ 0.0 IN. W.G.
(f)
3277
NO. MOTORS – HP
1 – 1/8
MOTOR SPEED R.P.M.
850
VOLTS/PH/HZ
208–230/1/60
F.L. AMPS
0.81
OUTDOOR COIL – TYPE
PLATE FIN
ROWS — F.P.I.
2 – 16
FACE AREA (SQ. FT.)
12.88
TUBE SIZE (IN.)
5/16
REFRIGERANT CONTROL
EXPANSION VALVE
REFRIGERANT
LBS. – R-410A (O.D. UNIT)
(g)
6 LBS, 13 OZ
FACTORY SUPPLIED
YES
LINE SIZE – IN. O.D. GAS
(h) (i)
7/8
LINE SIZE – IN. O.D. LIQ.
3/8
CHARGING SPECIFICATIONS
SUBCOOLING
8°F
DIMENSIONS
H X W X D
CRATED (IN.)
40.88 X 54.5 X 23.0
WEIGHT
SHIPPING (LBS.)
225
NET (LBS.)
198
(a)
Certified in accordance with the Air-Source Unitary Air-conditioner
Equipment certification program, which is based on AHRI standard
210/240.
(b)
Rated in accordance with AHRI standard 270.
(c)
Calculated in accordance with Natl. Elec. Codes. Use only HACR
circuit breakers or fuses.
(d)
This value shown for compressor RLA on the unit nameplate and on
this specification sheet is used to compute minimum branch circuit
ampacity and max. fuse size. The value shown is the branch circuit
selection current.
(e)
Use start components only when compressor is found to enter locked
rotor condition and will not start or when lights dim at compressor
start. No means no start components. Yes means quick start kit
components. PTC means positive temperature coefficient starter.
Optional kit shown.
(f)
Standard Air – Dry Coil – Outdoor
(g)
This value approximate. For more precise value see unit nameplate.
(h)
Reference the outdoor unit ship-with literature for refrigerant piping
length and lift guidelines. Reference the refrigerant piping software
pub # 32-3312-xx or refrigerant piping application guide SS-
APG006-xx for long line sets or specialty applications (xx denotes
latest revision).
(i)
The outdoor condensing units are factory charged with the system
charge required for the outdoor condensing unit, ten (10) feet of
tested connecting line, and the smallest rated indoor evaporative coil
match. Always verify proper system charge via subcooling (TXV/EEV)
or superheat (fixed orifice) per the unit nameplate.
Содержание 4TWL6036A1000A
Страница 4: ...4 4TWL6036A SF 1F EN Wiring Figure 1 2 0 3 0 3 5 Ton Models d159503p02...
Страница 5: ...4TWL6036A SF 1F EN 5 Figure 2 2 0 3 0 3 5 Ton Models W Wi ir ri in ng g...
Страница 6: ...6 4TWL6036A SF 1F EN Refrigerant Circuit Diagrams Figure 3 3 0 and 3 5 Ton Models Dwg D158717_RevB...
Страница 19: ...4TWL6036A SF 1F EN 19 Troubleshooting Does a resistance check show an open circuit between R and S...