background image

20 

 18-AC95D1-5C-EN

STEP 8

 - Verify typical performance.

Refer to System Pressure Curves in the Service 
Facts or on the label inside the control panel to 
verify typical performance.

STEP 6

 - Adjust refrigerant level to attain proper 

gage pressure.

Add refrigerant

 if the Liquid Gage Pressure is 

lower than the chart value.

1.  Connect gages to refrigerant bottle and 

unit as illustrated.

2.  Purge all hoses.
3.  Open bottle.
4.  Stop adding refrigerant when liquid line 

temperature and Liquid Gage Pressure 
matches the charging chart Final  
Subcooling value.

Recover refrigerant 

if the Liquid Gage Pressure 

is higher than the chart value.

20 MIN.

STEP 7 

-  Stabilize the system.

1.  Wait 20 minutes for the system condi-

tion to stabilize between adjustments.

Note: 

When the Liquid Line Temperature and 

Gage Pressure approximately match the chart, 
the system is properly charged.

2.  Remove gages.
3.  Replace service port caps to prevent 

leaks.  Tighten finger tight plus an  
additional 1/6 turn.

(Example only - see Service Facts)

PRESSURE CURVES FOR  4TWR3036B1000A

TAM4A0A36S31

TAM4A0A36S31

Cooling

Heating

DI

SCHARG

PRESSURE 

(PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

SUCTI

O

N

 PRESSURE 

(PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE.  MEASURE INDOOR WET BULB 
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES.  ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); 
LOCATE INDOOR WET BULB (2);  FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSURE IN LEFT 
COLUMN (4) or (5).

EXAMPLE: (1) OUTDOOR TEMP. 82 F. 

                  (2) INDOOR WET BULB 67 F.  

                  (3) AT INTERSECTION

ACTUAL: 

                  (4) DISCHARGE PRESSURE IS 315 PSIG

DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART

                  (5) SUCTION PRESSURE IS 135 PSIG

SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINES
GAS - 3/4" O.D.
LIQUID - 3/8" O.D.

DWG.NO. 4TWR3036B1

(2)

(5)

(3)

(1)

110

115

120

125

130

135

140

145

150

155

160

55

65

75

85

95

105

115

(2)

(4)

(3)

(1)

200

250

300

350

400

450

500

55

65

75

85

95

105

115

INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71, 
67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 

71, 67, 63 AND 59 DEG F.

40

50

60

70

80

90

100

110

120

130

140

150

160

-5

5

15

25

35

45

55

65

250

300

350

400

450

500

-5

5

15

25

35

45

55

65

INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM 80, 70, AND 60 
DEG F.

INDOOR ENTERING DRY BULB CURVESTOP TO BOTTOM 80, 70, AND 
60 DEG F.

Содержание 4TTX8024A

Страница 1: ...y approved matched indoor and outdoor systems All of the manufacture s split systems are AHRI rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and out...

Страница 2: ...t replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN or APP APG012 EN Extreme caution should be exercised when opening the L...

Страница 3: ...h of refrigerant lines from outdoor to indoor unit should NOT exceed 150 feet including lift 2 The maximum vertical change should not exceed 50 feet 3 Standard and alternate line sizes and service val...

Страница 4: ...oof top depending on local weather This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing Ensure that drain holes in unit base pan are not obstr...

Страница 5: ...pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The pad must be separate from any structure The pad must be level The pad should be h...

Страница 6: ...048A 7 8 3 8 7 8 3 8 150 50 4TTX8060A 1 1 8 3 8 7 8 3 8 150 50 ALTERNATE LINE SIZES Line Sizes Service Valve Connection Sizes Max Line Lift Lengths Vapor Line Liquid Line Vapor Line Connection Liquid...

Страница 7: ...mine required line length and lift You will need this later in STEP 2 of Section 14 Total Line Length __________ Ft Total Vertical Change lift __________ Ft The outdoor condensing units are factory ch...

Страница 8: ...rom the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hangers Isolation hangers should also be used wh...

Страница 9: ...e or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant L...

Страница 10: ...orrect direction of refrigeration flow away from outdoor unit and toward evapo rator coil as illustrated Braze the filter drier to the Liquid Line Continue the dry nitrogen purge Do not remove the wet...

Страница 11: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Le...

Страница 12: ...ete blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUN...

Страница 13: ...System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches t...

Страница 14: ...le stages of electric heat jumper W1 and W2 together if comfort control has only one stage of heat TEM6 only When using a BK enabled comfort control cut BK jumper and bypass Y1 and Y2 at the air handl...

Страница 15: ...ies Furnace NOTES 1 For PWM BK enabled thermostats cut the BK jumper on the IFC and connect wiring 2 The factory Y1 O jumper must remain in place for proper LED read out in cooling mode 3 Y1 and Y2 wi...

Страница 16: ...s STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is used and the Outdoor Ambient is below 70 F 60 M...

Страница 17: ...ent tempera ture is above 55 F For best results the indoor temperature should be kept between 70 F to 80 F STEP 1 Use the refrigerant line total length and lift measurements from Section 5 3 Total Lin...

Страница 18: ...CHARGING CHART CORRECTIONS TABLE FOR LINE LENGTH AND RISE Add 2 REFRIGERANT LINE LIFT FT 4 Ton AC 50 1 40 1 30 25 Use Design Subcooling 15 10 0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 REFRIGE...

Страница 19: ...essure should be ap proximately 327 PSIG This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 1...

Страница 20: ...R TEMPERATURE Degree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER INDO...

Страница 21: ...ured Suction Line Temp __________ F Liquid Gage Pressure __________ PSIG Suction Gage Pressure __________ PSIG Calculating Charge Using the Weigh In Method 1 Measure in feet the distance between the o...

Страница 22: ...btained with the namplate charge plus additional charge previously added STEP 5 Return to site for adjustment Important Return in the spring or summer to accurately charge the system in the cooling mo...

Страница 23: ...gainst the following list Final phases of this installation are the unit Operational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Importa...

Страница 24: ...A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N...

Страница 25: ...18 AC95D1 5C EN 25...

Страница 26: ...AHRI Certified mark indicates Trane U S Inc participation in the AHRI Certification program For verification of individual certified products go to ahridirectory org Trane has a policy of continuous d...

Отзывы: