background image

18 

 18-AC79D1-6-EN

STEP 8 - Verify typical performance.

Refer to System Pressure Tables in the Service 
Facts to verify typical performance.

STEP 6 - Adjust refrigerant level to attain 
proper gage pressure.

Add refrigerant if the Liquid Gage Pressure 
is lower than the chart value.

1.  Connect gages to refrigerant bottle 

and unit as illustrated.

2.  Purge all hoses.
3.  Open bottle.
4.  Stop adding refrigerant when liquid 

line temperature and Liquid Gage 
Pressure matches the charging chart 
Final Subcooling value.

Recover refrigerant if the Liquid Gage Pres-
sure is higher than the chart value.

(Example only - see Service Facts)

20 MIN.

STEP 7 -  Stabilize the system.

1.  Wait 20 minutes for the system condi-

tion to stabilize between adjustments.

Note: When the Liquid Line Temperature and 
Gage Pressure approximately match the chart, 
the system is properly charged.

2.  Remove gages.
3.  Replace service port caps to prevent 

leaks.  Tighten finger tight plus an ad-
ditional 1/6 turn.

PRESSURE CURVES FOR  4TTR3036D1000A

4TXCB036BC3

Cooling with Thermal Expansion Valve

L

IQ

U

ID

 PR

ESSU

R

E (

PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

SU

C

T

IO

N

 PR

ESSU

R

E (PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE.  MEASURE INDOOR WET BULB 
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES.  ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); 
LOCATE INDOOR WET BULB (2);  FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .

EXAMPLE: (1) OUTDOOR TEMP. 82 F. 
                  (2) INDOOR WET BULB 67 F.  
                  (3) AT INTERSECTION

ACTUAL: 

                  (4) LIQUID PRESSURE @ 1060 CFM IS 318 PSIG

LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART

                  (5) SUCTION PRESSURE @ 1060 CFM IS 133 PSIG

SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINES
GAS - 3/4 " O.D.
LIQUID - 3/8 " O.D.

100

105

110

115

120

125

130

135

140

145

150

155

160

165

170

40

50

60

70

80

90

100

110

120

200

250

300

350

400

450

500

550

40

50

60

70

80

90

100

110

120

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)

INDOOR ENTERING 
WET BULB CURVES
TOP TO BOTTOM 
71, 67, 63 AND 59 DEG F.

INDOOR ENTERING 
WET BULB CURVES
TOP TO BOTTOM 
71, 67, 63 AND 59 DEG F.

Содержание 4TTR3018-060

Страница 1: ...roved matched indoor and outdoor systems All of the manufacture s split systems are A H R I rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and outdoo...

Страница 2: ...ponent replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN or APP APG012 EN Extreme caution should be exercised when opening...

Страница 3: ...outdoor to indoor unit should NOT exceed sixty 60 feet 2 The maximum vertical change should not exceed sixty 60 feet 3 Service valve connection diameters are shown in Table 5 1 Note For line lengths...

Страница 4: ...from any structure to prevent excess roof runoff water from pouring directly on the unit STEP 2 To remove the unit from the pallet remove tabs by cutting with a sharp tool Section 3 Unit Preparation...

Страница 5: ...8 4TTR3036G 3 4 3 8 3 4 3 8 4TTR3042D 3 4 3 8 3 4 3 8 4TTR3048D 7 8 3 8 7 8 3 8 4TTR3060D 7 8 3 8 7 8 3 8 Section 5 Refrigerant Line Considerations 5 1 Refrigerant Line and Service Valve Connection Si...

Страница 6: ...ly with National State and Local Codes when isolating line sets from joists rafters walls or other structural elements Isolation From Joist Rafter Side View 8 Feet Maximum Secure Vapor line from joist...

Страница 7: ...or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant Li...

Страница 8: ...avoid heat damage and continue the dry nitrogen purge Braze the refrigerant lines to the service valves Continue the dry nitrogen purge Do not re move the wet rag until all brazing is completed Impor...

Страница 9: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Lea...

Страница 10: ...te blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUNT...

Страница 11: ...ve System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches...

Страница 12: ...per W1 and W2 together if comfort control has only one stage of heat Y for TEM3 and TEM4 Only applies for TEM6 Thermostat Air Handler Outdoor Unit R G B W1 W2 B Y R G B C Y W1 W2 Blue 24 VAC HOT FAN 2...

Страница 13: ...h Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be n...

Страница 14: ...s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is...

Страница 15: ...to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient tempera ture is above 55 F STEP 1 Use the refrigerant line total length and lift measurement...

Страница 16: ...LINE LENGTH FEET REFRIGERANT LINE LIFT FEET 10 20 25 30 40 60 Add 4 of Subcooling Add 3 of Subcooling Add 2 of Subcooling Add 1 of Subcooling Use Design Subcool Value 60 50 40 30 25 20 15 10 0 SUBCOOL...

Страница 17: ...ssure should be ap proximately 327 PSI This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 195...

Страница 18: ...OR 4TTR3036D1000A 4TXCB036BC3 Cooling with Thermal Expansion Valve LIQUID PRESSURE PSIG OUTDOOR TEMPERATURE Degree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECK...

Страница 19: ...heckout Procedures and Troubleshooting 15 1 Operational And Checkout Procedures CHECKOUT PROCEDURE After installation has been completed it is recommended that the entire system be checked against the...

Страница 20: ...R T R E L A Y C O N T A C T O R C O N T A C T S L O W V O L T A G E W I R I N G C O N T R O L T R A N S F O R M E R T H E R M O S T A T C O N T A C T O R C O I L L O W V O L T A G E F U S E S T U C K...

Отзывы: