18-BC98D1-1G-EN
11
Table 13.
Isolation From Joist/Rafter
8 Feet Maximum
Side View
8 Feet Maximum
Joist/Rafter
Isolator
Line Set
Secure Vapor Line from joists using isolators every 8 ft. Secure Liquid Line directly to insulated Vapor Line using tape, wire, or other appropriate
method every 8 ft.
Table 14.
Isolation In Wall Spaces
Side View
Isolator
Line Set
8 Feet Maximum
Wall
8 Feet Maximum
Secure Vapor Line from joists using isolators every 8 ft. Secure Liquid Line directly to insulated Vapor Line using tape, wire, or other appropriate
method every 8 ft.
Table 15.
Isolation Through Wall
Wall
Sealant
Insulation
Vapor Line
Duct Work
Isolator
Line Set
DO NOT hang line sets from duct work