32
18-AC126D1-1A-EN
Figure 9. 3.0 Ton Models
PRESSURE CURVES (Refer below table for models)
OUTDOOR TEMPERATURE (Degree F)
OUTDOOR TEMPERATURE (Degree F)
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
ACTUAL:
(4) LIQUID PRESSURE @ 600 CFM IS 307 PSIG
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 600 CFM IS 137 PSIG
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
105
110
115
120
125
130
135
140
145
150
155
160
165
170
50
60
70
80
90
100
110
120
(1)
170
220
270
320
370
420
470
520
50
60
70
80
90
100
110
120
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
Cooling
@SCFM
4TTL5036N1
OD Model
1000
71
67
63
59
L
IQ
U
ID
P
R
E
S
S
U
R
E
(
P
S
IG
)
S
U
C
T
IO
N
P
R
E
S
S
U
R
E
(
P
S
IG
)
Содержание 4TTL5024N1000A
Страница 27: ...18 AC126D1 1A EN 27 Wiring Diagrams Figure 4 2 0 2 5 and 3 0 Ton Models...
Страница 28: ...28 18 AC126D1 1A EN Figure 5 2 0 2 5 and 3 0 Ton Models W Wi ir ri in ng g D Di ia ag gr ra am ms s...
Страница 29: ...18 AC126D1 1A EN 29 Figure 6 3 5 and 4 0 Ton Models W Wi ir ri in ng g D Di ia ag gr ra am ms s...
Страница 30: ...30 18 AC126D1 1A EN Figure 7 3 5 and 4 0 Ton Models W Wi ir ri in ng g D Di ia ag gr ra am ms s...
Страница 34: ...34 18 AC126D1 1A EN N No ot te es s...
Страница 35: ...18 AC126D1 1A EN 35 N No ot te es s...