24
18-AC126D1-1A-EN
Charging the Unit
Table 26.
Stabilize the system
1.
Wait 20 minutes for the system condition to stabilize between
adjustments.
Note:
When the Liquid Line Temperature and Gage Pressure
approximately match the chart, the system is properly
charged.
2.
Remove gauges.
3.
Replace service port caps to prevent leaks. Tighten finger tight
plus an additional 1/4 turn.
20 MIN.
Table 27.
Proper Gage Pressure
Measure the liquid line temperature and pressure at the outdoor unit’s
service valve.
Measure Liquid Line Temp =
________________________°F
Liquid Gage Pressure =
________________________ PSI
Final Subcooling Value = ________________________ °F
107 °F
Table 28.
Verify Performance
4.
Refer to System Pressure Curves at the end of the document to
verify typical performance.
PRESSURE CURVE SAMPLE
Cooling @ 1450 SCFM
Heating @ 1350 SCFM
D
IS
C
H
A
R
G
E
P
R
E
S
S
U
R
E
(
P
S
IG
)
OUTDOOR TEMPERATURE (Degree F)
S
U
C
T
IO
N
P
R
E
S
S
U
R
E
(
P
S
IG
)
110
115
120
125
130
135
140
145
150
155
160
165
170
40
60
80
100
120
200
250
300
350
400
450
500
550
40
60
80
100
120
(1)
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
30
40
50
60
70
80
90
100
110
120
130
140
-5
5
15
25
35
45
55
65
200
250
300
350
400
450
500
-5
5
15
25
35
45
55
65
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
80, 70, AND 60 DEG F.
INDOOR ENTERING
DRY BULB CURVES
TOP TO BOTTOM
80, 70, AND 60 DEG F.
Содержание 4TTL5024N1000A
Страница 27: ...18 AC126D1 1A EN 27 Wiring Diagrams Figure 4 2 0 2 5 and 3 0 Ton Models...
Страница 28: ...28 18 AC126D1 1A EN Figure 5 2 0 2 5 and 3 0 Ton Models W Wi ir ri in ng g D Di ia ag gr ra am ms s...
Страница 29: ...18 AC126D1 1A EN 29 Figure 6 3 5 and 4 0 Ton Models W Wi ir ri in ng g D Di ia ag gr ra am ms s...
Страница 30: ...30 18 AC126D1 1A EN Figure 7 3 5 and 4 0 Ton Models W Wi ir ri in ng g D Di ia ag gr ra am ms s...
Страница 34: ...34 18 AC126D1 1A EN N No ot te es s...
Страница 35: ...18 AC126D1 1A EN 35 N No ot te es s...