Service Facts
IMPORTANT — This document contains a wiring diagram, a parts list, and service information. This is customer property and
is to remain with this unit. Please return to service information pack upon completion of work.
© 2013 Trane
NOTICE: The manufacturer
has a policy of continuous product and product data improvement
and
it reserves the right to change design and specifications without notice.
WARNING
!
THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS
POSSESSING ADEQUATE BACKGROUNDS OF ELECTRICAL AND
MECHANICAL
EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR
CONDITIONING PRODUCT MAY RESULT IN PERSONAL INJURY AND
OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT
BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION,
NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
CAUTION
!
RECONNECT ALL GROUNDING DEVICES.
ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING
ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING
WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED
TO COMPLETE A PATH TO GROUND ARE REMOVED FOR
SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL
POSITION AND PROPERLY FASTENED.
WARNING:
HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE
CAPACITORS BEFORE SERVICING
CAUTION
!
UNIT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING PRESSURE EXCEEDS THE
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS
REQUIRED. FAILURE TO USE PROPER SERVICE
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR
PERSONAL INJURY.
SERVICE
USE ONLY R-410A REFRIGERANT AND
APPROVED POE COMPRESSOR OIL.
PRODUCT SPECIFICATIONS
OUTDOOR UNIT
POWER CONNS.
— V/PH/HZ
1
MIN. BRCH. CIR. AMPACITY
BR CIR PROT RTG – MAX. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS
5
- L.R. AMPS
FACTORY INSTALLED
START COMPONENTS
6
INSUL/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G.
2
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL
— TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
REFRIGERANT CONTROL
LBS — R-410A (O.D. UNIT)
3
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS
4
LINE SIZE - IN. O.D. LIQ.
4
CHARGING SPECIFICATION
TXV SYS CHGD TO SUBCOOL
CAPILLARY SYS CHGD TO SUPERHEAT
DIMENSIONS
CRATED (IN.)
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
Tubing lengths in excess of sixty (60) feet see application software.
4TTA3AD-SF-1A
Split System
Cooling
4TTA3030AD000A, 4TTA3036AD000A, 4TTA3042AD000A,
4TTA3048AD000A, 4TTA3060AD000A
10/13
4TTA3042AD000A
380-415/3/50
12
21
SCROLL
1 - 1
380-415/3/50
6.9 - 52.0
NO
NO
YES
PROPELLER
27.6 - 1
DIRECT - 1
3525
1 - 1/6
700
380-415/3/50
0.7
SPINE FIN™
1 - 24
27.86
3/8
R-410A
TXV/Capillary
8 LBS., 6 OZ.
YES
7/8
3/8
10°F
10°F
H X W X D
46.4 x 35.1 x 38.7
277
240
4TTA3048AD000A
380-415/3/50
12
21
SCROLL
1 - 1
380-415/3/50
7.6 - 51.5
NO
NO
YES
PROPELLER
27.6 - 1
DIRECT - 1
3980
1 - 1/6
700
380-415/3/50
0.7
SPINE FIN™
1 - 24
30.79
3/8
R-410A
TXV/Capillary
9 LBS., 13 OZ.
YES
7/8
3/8
10°F
10°F
H X W X D
51 x 35.1 x 38.7
292
255
4TTA3060AD000A
380-415/3/50
14
25
SCROLL
1 - 1
380-415/3/50
8.9 - 67.1
NO
NO
YES
PROPELLER
27.6 - 1
DIRECT - 1
3980
1 - 1/6
700
380-415/3/50
0.7
SPINE FIN™
1 - 24
30.79
3/8
R-410A
TXV/Capillary
9 LBS., 14 OZ.
YES
7/8
3/8
10°F
10°F
H X W X D
51 x 35.1 x 38.7
297
260
4TTA3030AD000A
380-415/3/50
9
15
SCROLL
1 - 1
380-415/3/50
6.1 - 38.0
NO
NO
YES
PROPELLER
27.6 - 1
DIRECT - 1
3525
1 - 1/6
700
380-415/3/50
0.7
SPINE FIN™
1 - 24
24.93
3/8
R-410A
TXV/Capillary
7 LBS., 11 OZ.
YES
3/4
3/8
10°F
10°F
H X W X D
42.4 x 35.1 x 38.7
217
182
4TTA3036AD000A
380-415/3/50
11
19
SCROLL
1 - 1
380-415/3/50
6.7 - 43.0
NO
NO
YES
PROPELLER
27.6 - 1
DIRECT - 1
3525
1 - 1/6
700
380-415/3/50
0.7
SPINE FIN™
1 - 24
24.93
3/8
R-410A
TXV/Capillary
8 LBS., 8 OZ.
YES
7/8
3/8
10°F
10°F
H X W X D
42.4 x 35.1 x 38.7
254
219
TUBING INFORMATION
LINE TYPE
REFRIGERANT TO ADD AT SPECIFIED
ADDITIONAL LENGTH
Suction Liquid
20 ft
30 ft
40 ft
50 ft
60 ft
3/4"
3/8"
3 oz
9 oz
15 oz
21 oz
27 oz
7/8"
3/8"
3 oz
9 oz
16 oz
22 oz
28 oz
CONTAINS REFRIGERANT!
SYSTEM CONTAINS OIL AND REFRIGERANT UNDER
HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE
PRESSURE BEFORE OPENING SYSTEM.
Failure to follow proper procedures can result in personal
illness or injury or severe equipment damage.
CAUTION
!
HOT SURFACE!
DO NOT TOUCH TOP OF COMPRESSOR.
May cause minor to severe burning.
CAUTION
!
1
Calculated in accordance with Natl. Elec. Codes. Only use
HACR circuit breakers or fuses.
2
Standard Air — Dry Coil — Outdoor
3
This value approximate. For more precise value see unit nameplate.
4
Max. linear length 80 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid
60 ft. For greater length consult refrigerant piping software Pub.
No. 32-3312-0* (* denotes latest revision).
5
This value shown for compressor RLA on the unit nameplate
and on this specification sheet is used to compute minimum
branch circuit ampacity and max. fuse size. The value shown is
the branch circuit selection current.
6
No means no start components. Yes means quick start kit com-
ponents. PTC means positive temperature coefficient starter.