1234-TTT000-EN
15
Note:
For additional information on maximum piping length for these systems, please refer to
Application guide 32-3009-03.
Connection Pipe
13 SEER (60 Hz)
4MCW3509A1AA
4TTK3509A1AA
4MCW3512A1AA
4TTK3512A1AA
4MCW3518B1AA
4TTK3518B1AA
4MCW3524B1AA
4TTK3524B1AA
Refrigerant Charge (lbs)
2.2 (R-410A)
2.3 (R-410A)
4.84 (R-410A)
5.07 (R-410A)
Length (m)
8
8
8
8
Gas additional charge (g/m)
30
30
40
40
Connection
Outer
Diameter
Liquid Pipe (mm)
6 (1/4")
6 (1/4")
9.52 (3/8")
9.52 (3/8")
Pipe
Gas Pipe (mm)
12 (1/2")
12 (1/2")
16 (5/8")
16 (5/8")
Max
Distance
Height (m)
5
5
10
10
Length (m)
10
10
15
15