ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service information
pack upon completion of work.

Installer’s Guide

Condensing Units

2TTR2018-060, 2TTR1018-060 & 2TTR0060

These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation.  All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. 
 Should further information be
desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.

A. GENERAL

The following instructions cover 2TTR2, 2TTR1 & 2TTR0;
Condensing Units.

NOTE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve or
Accutron™  Flow Control Check Valve (F.C.C.V.) assembly
for refrigerant flow control only.

Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the
unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit.  The electrical power
available must agree with that listed on the nameplate.

B. LOCATION & PREPARATION OF THE UNIT

1. When removing unit from the pallet, notice the tabs on

the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).

2. The unit should be set on a level support pad at least as

large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin “Trane APB2001-02”.

3. The support pad must NOT be in direct contact with any

structure.  Unit must be positioned a minimum of 12"
from any wall or surrounding shrubbery to insure
adequate airflow.  Clearance must be provided in front of
control box (access panels) & any other side requiring
service access to meet National Electrical Code.  Also,
the unit location must be far enough away from any
structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close to
bedroom(s).

1

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight.  Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to

indoor unit should NOT exceed sixty (60) feet.

7. If outdoor unit is mounted above the air handler,

maximum lift should not exceed sixty (60) feet (suction
line).  If air handler is mounted above condensing unit,
maximum lift should not exceed sixty (60) feet (liquid
line).

NOTE:
Refer to “Refrigerant Piping Software” Pub. No. 32-3312-02.

8. Locate and install indoor coil or air handler in accor-

dance with instruction included with that unit.

5 FT. ABOVE UNIT-UNRESTRICTED

2TTR2-IN-1B

18-AC51D2-3

Содержание 2TTR2018-060

Страница 1: ...move tabs by cutting with a sharp tool as shown in Figure 2 see page 2 2 The unit should be set on a level support pad at least as large as the unit base pan such as a concrete slab If this is not the...

Страница 2: ...ant tubing INSIDE OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liquid and gas lines 5 Be sure the tubing is of sufficient length 6 Uncoil the tubing do not kin...

Страница 3: ...oap bubbles or other leak checking methods to see that all field joints are leak free If not release pressure then repair SYSTEM EVACUATION NOTE Since the outdoor unit has a refrigerant charge the gas...

Страница 4: ...r by closing the system main disconnect switch This will activate the compressor sump heat where used Do not change the Thermostat System Switch until power has been applied for one 1 hour Following t...

Страница 5: ...w voltage wiring to be No 18 AWG minimum conductor 4 ODT B must be set lower than ODT A 5 If outdoor thermostats ODT are not used connect W1 to W2 and W3 PRINTED FROM B152901 P02 PRINTED FROM B152908...

Страница 6: ...8 210 8 1 4 57 2 1 4 457 18 2TTR1048A 2 2 730 28 3 4 724 28 1 2 651 25 5 8 1 1 8 3 8 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTR1060A 3 1 933 36 3 4 829 32 5 8 756 29 3 4 1 1 8 3 8 143 5 5 8 92...

Страница 7: ...18 AC51D2 3 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152637 Rev 1...

Страница 8: ...ng 2 X X X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is rec...