background image

MS-SVN056C-EN

47

Wired Controller

Installation procedure

Wiring technique: 

Installation instructions

To use the remote control unit, install a 5-wire terminal block and adhere an infrarred emitter close 
to the switch receiver. Connect anode and cathode to A, B on the terminal board; c5V, GND, 
RUN coming from the switch independently from C, D, E of the 5-wire terminal block.

This board accepts 5-wire cable which length 
should match actual conditions.

Wired 

Remote Control

Terminal board

Terminal block protrudes from the 
back cover; a perforation is required 
to allow for correct mounting. 
It must not be connected directly
to the wall!

To join the front cover to 
the back side of the remote 
control, latch the first lug 
and then latch the other.

Wooden
screw (M4X20)

Control panel
     cover

Control panel

LCD screen

Remote control

   front cover

 

Remote control 

     back cover

To separate both parts pry borders

using the tip of a screwdriver

Remote control

Mounting screws B

ST2.9x10-C-H

CANCEL

LOCK

SET TEMPERATURE(°C)

AUTO
COOL
DRY
HEAT

FAN
HIGH
MED
LOW

TEMP

MODE

SWING

TIMER

RESET

ON/OFF

  FAN 
SPEED

VENT

ECONOMIC 
 RUNNING

Содержание 2MCC05-C

Страница 1: ...usted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels...

Страница 2: ...for CFCs and HCFCs such as saturated or unsaturated CFCs and HCFCs Important Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment ou...

Страница 3: ...ng this unit technicians MUST put on all PPE required for the work being undertaken example cut resistant gloves sleeves butyl gloves safety glasses hard hat bump cap fall protection electrical PPE an...

Страница 4: ...em Appearance 13 Indoor unit Convertible 13 Cassette Unit Installation 14 Location 14 Concealed Unit Installation 21 Location 21 Convertible Unt Installation 28 Outdoor Unit Installation 32 Location 3...

Страница 5: ...VN056C EN 5 Wired Controller 49 Installation procedure 50 Accessories provided for installation 52 Cassette unit 52 Concealed unit 53 Convertible unit 54 Wiring Diagrams 55 U Match Unit interconnectio...

Страница 6: ...eport same in writing to the transportation company within 72 hours of delivery At the same time notify your local sales representative of these damages Inspect the unit within the first 7 days of del...

Страница 7: ...U Hr Single split system cooling only fixed speed Heat pump fixed speed Indoor Unit Outdoor Unit Cassette 2MCC05 C 4TTK05 D Concealed 2MCZ05 C 4TTK05 D Convertible 2MCX05 C 4TTK05 D Indoor Unit Outdoo...

Страница 8: ...least 1 meter in distance in order to avoid fire or explosion hazards Never try to repair the air conditioning unit by yourselves An erroneous repair could lead to electrocution or fire Always call y...

Страница 9: ...0 11 11 12 1 5 7 8 2 4 6 RESET TIME ON TIME OFF CLO CK SWI NG AIR DIREC TION OK ECO SWI NG MOD E FAN SPE ED LOCK C H AUT O COO L DRY HEA T FAN TEM P SET CLOCK SET HOUR FAN SPEED Indoor Unit Outdoor Un...

Страница 10: ...image since they may differ from the actual unit acquired by the customer Indoor Unit Outdoor Unit A B C 1 Outgoing air 7 Connecting piping 2 Incoming air 8 Incoming air 3 Air filter 9 Incoming air s...

Страница 11: ...merely representative of their image since they may differ from the actual unit acquired by the customer Indoor Unit Outdoor Unit A B C 1 Outgoing air 7 Connecting piping 2 Mesh filter nylon 8 Incomi...

Страница 12: ...air to reach the space designated for air conditioning Easy removal of all connecting and draining piping Space devoid of radiation and heat sources Note Keep the unit at a distance of at least 1 met...

Страница 13: ...the correct balance of the unit Place the drain pipe in the right direction to allow it to adjust to the movement of the water level controller Center the unit in a manner that may ensure uniform spac...

Страница 14: ...ng scratched 1 Air grill removal Slide both sliding bars simultaneously towards the center and then lift them Lift the air grill at an angle of 45 degrees and remove it 2 Remove the 4 corner installat...

Страница 15: ...ly 4 to 6 mm The edge of the panel must touch the ceiling Failure in the operation of the unit may be due to inappropriate adjustment of the panel screw If after adjustment of the installation screws...

Страница 16: ...panel 1 outgoing air fan foam rubber on panel 2 4 m m 6 foam rubber on the outlet Leak Ceiling Contamination Condensation leaking Loosen top screw Adjust lower screw Spacing forbidden Tapping screw on...

Страница 17: ...nit in cooling mode The operation of the pump will be heard during testing Verify that water drains correctly 1 minute delay depending upon the length of the drain tube Confirm that all pipe fittings...

Страница 18: ...n the case of double duct connection the original opening for outgoing air with the same piping direction must be sealed Double duct connection Ductwork air volume is approximately 200 260m3 h Model 1...

Страница 19: ...from these devices Clearance for maintenance procedures Hanging rods installation 4 Consult the following diagrams to determine the distance in between hanging rods Use threaded rods of 10mm dia 0 39...

Страница 20: ...ngs Use threaded rod eye bolt or reinforced lug Steel beam ceilings Install using a steel support angle Hanging the unit Hang the unit from the threaded rods and fasten it with the corresponding nuts...

Страница 21: ...ure table Change the motor static pressure of the ventilator so that it may correspond to the ductwork static pressure Note 1 Avoid any weight of the canvas over the indoor unit 2 Use non flammable ca...

Страница 22: ...mension in mm Opening size for outgoing air Opening size for air return Size of mounting tab A B C D E F G H I J 18 880 34 6 210 8 3 674 26 5 600 23 6 136 5 4 706 27 8 190 7 5 782 30 8 920 36 2 508 20...

Страница 23: ...e Position ON is the field selection for cooling only mode Side rail 1 Remove ventilation panel and flanges and cut the clamps from the side rail 2 Paste the foam rubber protector in the place as show...

Страница 24: ...24 MS SVN056C EN Concealed Unit Installation Performance Curves...

Страница 25: ...MS SVN056C EN 25 Concealed Unit Installation...

Страница 26: ...f outdoor air currents Appropriate capacity to allow the flow of air to reach the space designated for air conditioning Easy removal of all connecting and draining piping Space devoid of radiation and...

Страница 27: ...piping with outlet towards the outside of the suspended ceiling Before installing the machine determine connecting points for refrigerant lines drain piping and indoor and outdoor unit lines Wooden c...

Страница 28: ...tall using a steel support rafter beam Unit installation Remove side panels and grille Place hanging anchors over the hanging rods Anchor bolt Steel support rafter Hanging rods Side panel Grille Hangi...

Страница 29: ...all installation 20mm D Refrigerant line connection D gas side Draining point Downward pitch between 1 2 100 E Refrigerant line connection E liquid side Unit dimensions unit mm MODEL 24 18 A B D E C 1...

Страница 30: ...of supporting the weight of the outdoor unit and prevent the transmission of noise and vibrations Easy access to piping and wiring installations Unobstructed outlet for discharge air Free from fire ha...

Страница 31: ...ations Outdoor unit dimensions mm Mounting dimensions mm inch Capacity H x W x D Distance A Distance B 12K 770 x 555 x 300 487 19 17 298 11 73 18K 24K 845 x 702 x 363 540 21 26 350 13 8 36K 946 x 810...

Страница 32: ...or with any other objects Do not pitch the unit more than 45 and do not place it on its side Mount the unit on a concrete base following proper specifications Use screws to install the unit securely i...

Страница 33: ...ounting base Install the unit to the base with M10 anchor bolts In installations on the roof or balcony avoid draining the unit towards areas of human crossing 100 3 94in 100 300 3 94 11 81in No Descr...

Страница 34: ...10m 32 8 pies Condensing unit Liquid line mm inch Gas line mm inch One stage outdoor units 4TTK0512D1000AL 6 35 1 4 12 7 1 2 4TTK0518D1000AL 6 35 1 4 12 7 1 2 4TTK0524D1000AL 9 52 3 8 15 9 5 8 4TTK05...

Страница 35: ...fy the absence of any leaks Check all couplings with a leak detector or with the use of soapy water 7 Cover all line couplings with pipe a sleeve made of insulation material and further cover these co...

Страница 36: ...refore before the final connection purge air from the refrigerant line Purge air after connecting the refrigerant line to both indoor unit and outdoor unit Tighten nuts on the service valves Fold the...

Страница 37: ...lings with pipe a sleeve made of insulation material and further cover these couplings with the appropriate insulation material to avoid leaks 4 Air purging Loosen and remove nuts from A and B shutoff...

Страница 38: ...h gas and liquid shutoff valves should be maintained in closed position After 2 hours or more of operation ensure that the pump reaches a 0 1MPa reading or less If after 3 hours of operation the pump...

Страница 39: ...it which consequently will provoke condensate overflow Drain pipe height from the ground to the end of the tube should be more than 50mm Do not place the end of the drain pipe in water For condensate...

Страница 40: ...n into consideration during installation procedures in order to prevent any corrosion on the bottom of the equipment Ascertain that outdoor unit is able to drain condensate water appropriately in heat...

Страница 41: ...replaced by the manufacturer or by its service agent or by qualified personnel Electrical wiring connection 1 Remove screws from the electrical cover Should there be no electrical cover on the outdoor...

Страница 42: ...ition on gas and liquid sides Air conditioning unit preheated through supply of electric heat Install remote controller support in appropriate place from which spot the signal can easily reach the ind...

Страница 43: ...1 Phase 1 Phase 1 Phase 1 Phase 1 Phase 3 Phase 3 Phase Voltage 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase 208 240V 208 240V Circuit breaker fuse A 20 16 40 30 60 40 70 55 70 60 32 25 45 35 Model 18 24...

Страница 44: ...age 208 240V 208 240V 208 240V 208 240V 208 240V Circuit breaker fuse A 25 20 32 25 50 40 70 55 70 60 Model 12 18 24 36 48 60 Voltage Phase 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase Voltage 208 240V 208...

Страница 45: ...hase 1 Phase 1 Phase 1 Phase 3 Phase 3 Phase Voltage 208 240V 208 240V 208 240V 208 240V 208 240V 208 240V 208 240V Circuit breaker fuse A 20 16 40 30 60 40 70 55 70 60 32 25 45 35 Model 18 24 36 48 6...

Страница 46: ...f the remote control unit Verify that you have availability to the following required materials NOTICE This document shows the procedure for installing the wired remote controller Refer to the indoor...

Страница 47: ...ired Remote Control Terminal board Terminal block protrudes from the back cover a perforation is required to allow for correct mounting It must not be connected directly to the wall To join the front...

Страница 48: ...Front of indoor unit Indoor unit electric junction box Electric box with 10 connecting poles Main board Terminal block signal receptor Signal receptor Group of connecting 10 wire cables Group of conn...

Страница 49: ...o direct sun rays or heat source When charging batteries verify proper polarity QUANTITY DRAWING NAME 13 Expansion anchor 3 Protector for external piping 4 Support ring for external pipe 5 Drain cap i...

Страница 50: ...utdoor unit installation 17 Connector transfer 6 35 9 52 packed together with unit NOTE Tube size differs depending on model Connector is needed to comply with tube size requirements for outdoor unit...

Страница 51: ...allation Convertible unit QUANTITY DRAWING NAME 5 User Manual 6 Installation Manual 7 Remote Control Manual Remote control unit in some models 2 Remote control housing in some models 4 Battery AAA 1 5...

Страница 52: ...5 3 63 2 5 1 525 287387 21 2 8 7 7 7 3 6 3 6 7 1 CN23 1 To CCM Comm Bus 1 1 5 1 1 1 21 2 5 5 1 8 5 1 5 1 5 2 N1 C1 32 5 3 6 72 287 225 81 7 1 225 5 1 5 0 2 1 0 3 3803 7 0 1 7 1 225 1 3 725 7 5 9 6 7...

Страница 53: ...M Comm Bus 1 1 5 1 1 1 21 2 5 5 1 8 5 1 5 1 5 2 N1 C1 32 5 6833 3 6 72 287 225 81 7 1 225 5 1 5 0 2 1 0 3 3803 7 0 1 7 1 225 1 3 725 7 5 9 6 7 3803 6 1 02725 3 62 76 3 3 1 225 1 1 6 6 211 725 5220 7 0...

Страница 54: ...525 287387 21 2 8 7 7 7 3 6 3 6 7 1 CN23 1 To CCM Comm Bus 1 1 5 1 1 1 21 2 5 5 1 8 5 1 5 1 5 52 1 2 N1 C1 32 5 3 6 72 287 225 81 7 1 225 5 1 5 0 2 1 0 3 3803 7 0 1 7 1 225 1 3 725 7 5 9 6 7 3803 6 1...

Страница 55: ...525 287387 21 2 8 7 7 7 3 6 3 6 7 1 CN23 1 To CCM Comm Bus 1 1 5 1 1 1 21 2 5 5 1 8 5 1 5 1 5 52 1 2 N1 C1 32 5 3 6 72 287 225 81 7 1 225 5 1 5 0 2 1 0 3 3803 7 0 1 7 1 225 1 3 725 7 5 9 6 7 3803 6 1...

Страница 56: ...7 1 CN23 1 To CCM Comm Bus 1 1 5 1 1 1 21 2 5 5 1 8 5 1 5 1 5 2 N1 C1 8 32 5 6833 3 6 5 1 F1 V1 72 287 225 81 7 1 225 5 1 5 0 2 1 0 3 3803 7 0 1 7 1 225 1 3 725 7 5 9 6 7 3803 6 1 02725 3 62 76 3 3 1...

Страница 57: ...CN5 WATER LEVEL SWITCH J7 CN23 ON OFF Remote Control AC FAN CAP Y G WHITE WHITE GRAY CN4 P1 P2 BLACK BROWN M 5 3 NOTE 1 The parts with dotted line indicates optional features 2 Remove the short connec...

Страница 58: ...WATER LEVEL SWITCH J7 CN23 ON OFF Remote Control AC FAN CAP Y G WHITE WHITE GRAY CN4 P1 P2 BLACK BROWN M 5 3 NOTE 1 The parts with dotted line indicates optional features 2 Remove the short connector...

Страница 59: ...1 5 0 211 7256 211 7256 3 3 7 03 6 1625 5220 7 03 6 1625 3 2 5 62 76 75 16 250 5 32 5 1 9 6 1 02725 2 1 225 1 1 225 1 3 3 57 1 0 5 1 5 8 5 1 1 3 6 3 6 57 57 72 5 21752 5 0 3 80 6 1 02725 7 1 5 75 16...

Страница 60: ...544 589 6 6 36 9 4958 8553 36 9 4958 6 5 8 95 1 9 8 49 583 8 65 8 2 2 9 4 35 58 5 4 558 4 4 558 4 6 6 8 4 3 4 8 8 1 2 2 8 1 3 6 3 6 57 57 72 5 21752 5 3 62 3 9 4 35 58 7 4 8 8 49 583 8 1 3 7 7 3 6 1 3...

Страница 61: ...UE COMP C R M S BLUE 1 2 N OUTDOOR UNIT BK BLACK CAPACITOR FAN MOTOR BLACK RED OVERLOAD RELAY INTERNAL EXTERNAL DEPENDING ON MODELS RED This symbol indicates the element is optional the actual shape s...

Страница 62: ...D OVERLOAD RELAY internal or external component C S R Y G PTCR BLACK BLACK BLACK BLUE M CODE PART NAME COMP CAP1 FAN CAP2 XT1 2 XT3 KM1 COMPRESSOR COMPRESSOR CAPACITOR OUTDOOR FAN TERMINALS MIDDLE TER...

Страница 63: ...725 287 225 1 OUTDOOR WIRING DIAGRAM 7 203 0 3 1 2 3 57 1 0 203 C S R CAP2 1 BLUE BLUE CAP1 RED WHITE BLACK BLACK POWER TO INDOOR UNIT 3 287 225 1 3 1 XT2 XT1 7 50 1 Y G 24V RED BLUE BLUE 1 A1 A2 L1 T...

Страница 64: ...PE TEMP SENSOR TRANSFORMER T5 K1 CONNECTOR HIGH LOW PRESSURE SWITCH AC CONTACTOR CONNECTORS RT3 XP7 9 H L PRO XT5 6 KM1 MAIN CONTROL BOARD RT3 CN206 CN201 XT5 XP8 XS8 CN100 CN208 CN200 KM1 A1 3 1 5 A2...

Страница 65: ...6 257 1 678 5220 7 03 6 1625 75 16 250 5 7 50 1 7 7 57 7 50 1 211 725 2 35 6685 6 7 6 257 1 678 5 1 217 725 3 3 7 03 6 1625 211 7256 57 3 352 7 7 0 7 5 0 1 21752 2 5 57 1 1 7 3 6 1 1 1 0 1 7 5 1 5 0 1...

Страница 66: ...6C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 12K 1 Phase 5 72 1 225 81 7 9 9 7 8 8 203 8 5 7 6 2035 6625 3 725 5 1 5 0 287 225 81 7 7 5 1 2 N 3 4 E T3 CAP2 BLUE M RED 3 6 RT3 RES...

Страница 67: ...BLACK BLACK BLACK RED 1 1 1 RED 1 1 1 3 RED POWER SUPPLY TO INDOOR UNIT 7 7 7 75 16 3 3 1 32 5 75 16 250 5 5220 7 03 5 785 3 3 7 03 5 785 855 17 7 7 5 1 5 0 287 225 81 7 2 3 57 1 0 287 225 1 02725 3...

Страница 68: ...1 7 3 WHITE 1 BLACK XP2 XS2 5 5 1 1 T3 XS3 XP3 XS4 XP4 BLUE T4 6 1 1 NOTICE FACTORY SETTING BLUE S V BLUE BLACK 2 4 7 3 6 7 7 75 16 3 1 32 5 75 16 250 5 3 3 7 03 5 785 5 6 6725 855 17 7 7 211 7256 LOW...

Страница 69: ...TOR HIGH LOW PRESSURE SWITCH AC CONTACTOR CONNECTORS RT3 XP7 9 H L PRO XT5 6 KM1 MAIN CONTROL BOARD RT3 CN206 CN201 XT5 XP8 XS8 CN100 CN208 CN200 KM1 A1 3 1 5 A2 2 4 6 CN203 T5 WIRING DIAGRAM FAN CAP...

Страница 70: ...5220 7 03 6 1625 75 16 250 5 7 50 1 7 7 57 7 50 1 211 725 2 35 6685 6 7 6 257 1 678 5 1 217 725 3 3 7 03 6 1625 211 7256 57 3 352 7 7 0 7 5 0 1 21752 2 5 57 1 1 7 3 6 1 1 1 0 1 7 3 725 2035 6625 287...

Страница 71: ...MS SVN056C EN 71 Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 36K 3 Phase...

Страница 72: ...72 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 48K 3 Phase...

Страница 73: ...MS SVN056C EN 73 Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 60K 3 Phase...

Страница 74: ...74 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 36K 3 Phase...

Страница 75: ...MS SVN056C EN 75 Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 48K 3 Phase...

Страница 76: ...76 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 60K 3 Phase...

Страница 77: ...ipci n Bornes C1 Compresor N1 C mun de 24 VAC V1 V lvula de 4 v as F1 Se al para ven dor exterior Puesta a erra C1 V1 N1 F1 C1 V1 N1 F1 Unida Exterior U Ma tc h I nte rc onex i n FRIO SOLO Unidad Inte...

Страница 78: ......

Страница 79: ......

Страница 80: ...e the quality and confort of air in homes and buildings transport and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of...

Отзывы: