product with radiation in the room is powered off.
The maintenance area should be equipped with a drying powder or carbon dioxide fire extinguisher and
that such fire extinguisher can work.
(2) Inspection of maintenance equipment
Check the maintenance equipment is applicable to the refrigerant or not and it is only allowed to use
the professional equipment recommended by the air conditioner manufacturer.
Check the refrigerant leak detector whether has been calibrated. The set maximum alarm concentration
of the refrigerant leak detector should not exceed 25% of the lower explosion limit (LEL), the refrigerant
leak detector must be working during maintenance.
2) Inspection of air conditioner
It is necessary to ensure that the air conditioner is in reliable ground connection before maintenance.
Make sure powered supply to air conditioner is off. Before maintenance, it is necessary to cut off the
power and discharge the capacitor power which used in the air conditioner. If it is a must to need the
power supply during the maintenance, it is necessary to do ongoing leak detection at the most
dangerous position/point in order to avoid potential danger.
Check the warning labels on the air conditioner whether are in good condition. It is necessary to replace
the damaged or smeared warning labels.
3). Leak inspection before maintenance
Before maintenance, use the leak detector or concentration detector (pump-type) recommended by
the corresponding air conditioner manufacturer to check the air conditioner leak or not.
Warning
If leak may exist, it is necessary to move all the fire out from the site or extinguish fire and then
immediately shut off the air conditioner. Meanwhile, it is necessary to make sure well-ventilated.
4). Safety principles during the maintenance
At the time of maintenance, it is necessary to ensure well-ventilation on the site.
It is prohibited to use fire including welding, smoking or other purposes. It is prohibited to use
mobile phones.
At the time of maintenance, if the relative humidity is lower than 40%, it is necessary to wear anti-
static clothing and gloves.
If the combustible refrigerant is found leaking during the maintenance, it is a must to immediately
take forced ventilation and plug up the leak source.
If the product is damaged to the extent that it is a must to open the refrigerating system for
maintenance, it is a must to carry the product back to the maintenance station for maintenance. (It
is prohibited to weld the refrigerant pipe and do o
ther operations on the user’s site.)
It is necessary to return the air conditioner to its initial state if it is necessary to provide visiting
service again due to lacking spare part during the maintenance. Moreover, it is a must to ensure
that the refrigerating system is in secure ground connection.
If it is necessary to provide visiting service with a refrigerant cylinder, the volume of refrigerant filled
in such refrigerant cylinder should not exceed the stipulated value. When such cylinder is stored in
a vehicle or placed on the installation or maintenance site, it is necessary to place it vertically and
securely and keep it away from any place where there is any heat source, combustion source,
radiation source or electrical equipment.
5). Requirements for the site of maintenance-station
The maintenance location should be well-ventilated, with leveled ground and not in a basement.
The maintenance should be divided into welding and non-welding areas both of which should be
Air Conditioner Service Manual
21
Содержание 09CH-FIXED-A1
Страница 6: ...Wiring diagram MODEL 75 1 2 75 1 2 75 1 2 INDOOR UNIT OUTDOOR UNIT Air Conditioner Service Manual 5...
Страница 7: ...MODEL 75 1 2 INDOOR UNIT Air Conditioner Service Manual OUTDOOR UNIT 6...
Страница 8: ...Air Conditioner Service Manual MODEL 75 1 75 1 75 1 INDOOR UNIT OUTDOOR UNIT 7...
Страница 9: ...Air Conditioner Service Manual MODEL 75 1 INDOOR UNIT OUTDOOR UNIT 8...
Страница 36: ...Air Conditioner Service Manual SORVLRQ YLHZ DQG SDUWV OLVW RPLW 35...