background image

SS-SVN11A-EN

11

Note:

 

Insulate all refrigerant piping 

and connections.

Refrigerant Piping Procedures 
(Outdoor Units)

Each CTA unit ships with a holding 
charge of dry nitrogen. The nitrogen 
should be removed and the entire sys-
tem evacuated (at the proper time) to 
avoid possible contamination.

1. Remove the service access panel.

2. Locate the liquid and discharge 

lines. Check that the piping connec-
tion stubs on the valves (Figure 6) 
line up properly with the holes in 
the unit cabinet.

Figure 6

3. Locate the gauge ports on the dis-

charge and liquid lines. Depress the 
valve core to release the nitrogen 
from the unit.

Note: If nitrogen is not released from 
the unit, there is a leak in the system. 
Locate the leak and repair before pro-
ceeding with the installation.

4. Unbraze the tube seal caps to reveal 

the line braze connections.

WARNING:

 

HAZARDOUS PRESSURES!
Coil has a nitrogen holding 
charge. Do not remove seal caps 
by heating the caps while coil is 
under pressure. Depress the 
gauge port valve cores to gradu-
ally relieve nitrogen holding 
charge. Remove valve cores 
before removing the tubing seal 
caps. Failure to properly relieve 
pressure could result in serious 
injury.

CAUTION:

 

Equipment Damage!
Do not remove the seal caps from 
refrigerant connections until pre-
pared to braze refrigerant lines to 
the connections. Excessive expo-
sure to atmosphere may allow 
moisture or dirt to contaminate 
the system, damaging valve seals 
and causing ice formation in sys-
tem components.

5. Cut, fit and braze tubing, starting at 

the outdoor unit and work toward 
the indoor unit.

Note: Use long radius bells for all 90 
degree bends.

All brazing should be done using a 2 
to 3 psig dry nitrogen purge flowing 
through the pipe being brazed (Figure 
6).

WARNING:

HAZARDOUS PRESSURES!
When using dry nitrogen cylin-
ders for pressurizing units for 
leak testing, always provide a 
pressure regulator on the cylinder 
to prevent excessively high unit 
pressures. Never pressurize unit 

above the maximum recom-
mended unit test pressure as 
specified in applicable unit litera-
ture. Failure to properly regulate 
pressure could result in a violent 
explosion, which could result in 
death or serious injury or equip-
ment or property-only-damage.

CAUTION:

 

Equipment Damage!
Wet-wrap all valves and protect 
painted surfaces from excessive 
heat. Heat can damage system 
components and the unit finish.

6. Shut off nitrogen supply.

7. Shut off the manifold valve for the 

line that is connected to the dis-
charge line gauge port. 

Figure 7

Installation

Содержание 090A***A - 60 HZ

Страница 1: ...SS SVN11A EN Models A and later Design Sequence Installation Owner Diagnostics Split System Cooling Condensers Model CTA 7 1 2 to 15 Tons CTA 090A A 60 HZ 120A A 60 HZ 120B A 60 HZ 180B A 60 HZ...

Страница 2: ...eri enced HVAC technicians to properly diagnose and repair this equipment NOTICE Warnings and Cautions appear at appropriate sections throughout this manual Read these carefully WARNING Indicates a po...

Страница 3: ...nit Inspection 9 Initial Leak Test 9 Lifting Recommendations 9 Clearances 10 Unit Mounting 10 Refrigerant Piping 10 Leak Check 12 System Evacuation 12 Refrigeration Charging 12 Electrical Wiring 13 Lo...

Страница 4: ...ial number and DL number if applica ble stamped on the unit nameplate Digits 1 2 3 Product Type CTA Remote Air Cooled Condenser Digits 4 5 6 Nominal Gross Cooling Capacity MBh 090 090 MBh used with 3...

Страница 5: ...SS SVN11A EN 5 Figure 1 CTA090A Figure 2 CTA120A Unit Dimensions...

Страница 6: ...6 SS SVN11A EN Figure 3 CTA120B Unit Dimensions...

Страница 7: ...SS SVN11A EN 7 Figure 4 CTA180B Unit Dimensions...

Страница 8: ...6 15 15 1 1 2 1 6 3 7 CTA090A8 575 60 1 518 632 15 15 1 1 2 1 2 3 0 CTA120A1 208 230 60 1 187 254 15 15 1 1 6 0 17 0 CTA120A2 460 60 1 414 506 15 15 1 1 2 7 7 0 CTA120A8 575 60 1 518 632 15 15 1 1 2 0...

Страница 9: ...5 days If concealed dam age is discovered stop unpacking the shipment Do not remove dam aged material from the receiving location Take photos of the dam age if possible The owner must provide reasonab...

Страница 10: ...y due to structural fail ure and can seriously damage the unit and the building Ground Level Mounting For ground level installation the unit base should be adequately supported and hold the unit near...

Страница 11: ...lt in serious injury CAUTION Equipment Damage Do not remove the seal caps from refrigerant connections until pre pared to braze refrigerant lines to the connections Excessive expo sure to atmosphere m...

Страница 12: ...ines leading to a sealed sys tem can be accomplished with manifold center hose and connecting branch hose to cylinder of R 410a and vacuum pump 3 Attach center hose of manifold gauges to the vacuum pu...

Страница 13: ...is operating properly 5 Disconnect all power to the unit WARNING HAZARDOUS VOLTAGE w CAPACITORS Disconnect all power including remote disconnects and dis charge all capacitors before ser vicing Follo...

Страница 14: ...ire 24 volts D 2 control wires 24 volts CTA180B S C I RH120 CTA180B S C I RH150 Field Wiring A 2 power wires Line voltage for single phase B 3 power wires Line voltage for 3 phase C Cooling only therm...

Страница 15: ...SS SVN11A EN 15 Field Wiring...

Страница 16: ...16 SS SVN11A EN Wiring...

Страница 17: ...SS SVN11A EN 17 Wiring...

Страница 18: ...18 SS SVN11A EN Wiring...

Страница 19: ...SS SVN11A EN 19 Wiring...

Страница 20: ...20 SS SVN11A EN Refrigeration Diagram Figure 11 Typical Split System Cooling Diagram...

Страница 21: ...rformed initial leak test Connected properly sized and con structed liquid and discharge lines to the connection stubs at both the indoor and outdoor units Insulated the entire discharge line Insulate...

Страница 22: ...ON AUTO switch on the room ther mostat With the switch positioned at AUTO and the system operating in the cooling mode fan operation coin cides with the cooling run cycles If the system is equipped w...

Страница 23: ...ct power before servic ing could result in death or seri ous injury 1 Inspect air filters and clean if neces sary 2 Check unit wiring to ensure all con nections are tight and that the wir ing insulati...

Страница 24: ...each inspection once per month during cooling season while unit is operating Date Ambient Temp F Evaporator Entering Air Compressor Superheat Subcooling Dry Bulb Wet Bulb Suction Pressure Discharge P...

Страница 25: ...exceed 18 months from shipment Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of standard 1 year coverage through the fifth year T...

Страница 26: ...gn and specifications without notice Literature Order Number SS SVN11A EN File Number SV UN SS SVN11A 1004 Supersedes New Stocking Location Inland Trane A Business of American Standard Companies www t...

Отзывы: