CVHE-SVX005B-EN
29
Figure 8. Chiller foot and isolator orientation
Side View of Unit
End View of Unit
Center
tube sheet
support leg
Outside
edge of
tube sheet
Center of
isolator
spring
Note: The spring isolator must be
centered in relation to the tube sheet.
Do not align the isolator with the flat
part of the chiller foot since the tube
sheet is often off center.
Note: The length of the
isolator should be parallel
to the leg.
IIm
mp
po
orrtta
an
ntt:: Do NOT install spring isolators or brackets
in such a way that they could inhibit chiller
servicing such as charging or evacuation,
oil tank service, etc.
Leveling the Unit
The chiller must be set level within 1/16 in. (1.6 mm).
1. Measure and make a punch mark an equal distance
up from the bottom of each foot of the chiller.
2. Suspend a clear plastic tube along the length of the
chiller as shown in the following figure.
3. Fill the tube with water until the level aligns with
the punch mark at one end of the chiller.
4. Check the water level at the opposite mark. If the
water level does not align with the punch mark, use
full length shims to raise one end of the chiller until
the water level at each end of the tube aligns with
the punch marks at both ends of the chiller.
5. Once the unit is level across its length, repeat the
first three steps to level the unit across its width.
Figure 9. Leveling the chiller
1
2
N
No
otte
e:: Use of a laser level is an acceptable alternative
method to level the unit.
IIm
mp
po
orrtta
an
ntt:: Immediately report any unit damage
incurred during handling or installation at
the job site to the Trane sales office.