Figure 59.
Fan motor and sheave adjustment
1.
2
3
1
Belt
2.Adjustment Bolt and
Plate
3.Sheave
Figure 60.
Units with Deluxe 24V or Tracer
®
ZN524
controls and ECM motors – DIP switch
settings
Dip switch to
select profile
Installation
WSHP-SVX01W-EN
61
Note:
EXH/V 0.5 to 6 ton high efficiency units only: Units
are shipped from the factory on profile setting B.
To adjust the cfm, disconnect the power to the unit. Set the
DIP switch located in the control box to the desired profile
setting. Connect the power to the unit.
Profile A = 110% of rated airflow
Profile B = 100% of rated airflow
Profile C = 90% of rated airflow
Profile D = 80% of rated airflow
Installation at higher altitudes may require an adjustment
to the fan speed setting to achieve proper airflow. Use
profile C or D to get lower airflow. If a lower CFM is needed,
then set DIP switch 4 to ON.
Figure 61.
Units with UC400 controls and ECM motors
– DIP switch settings
Installations at altitudes above 2000 feet may require an
adjustment to the fan speed setting to achieve the proper
airflow. To adjust the airflow to get the desired CFM, set the
DIP switches located in the control box to the proper
profile setting. Tracer
®
TU can be used to make further
adjustments to the fan speed.
Use the following table to select the correct profile to use.
Table 44. Profiles for altitude range
Profile
Altitude (Feet)
A
0–2000
B
2000–4000
C
4000–6000
D
Above 6000