START-UP DELAY:
The delay after powering on the unit during which the alarms
will not be generated.
The setup range is 0…60 s.
•
MODBUS ADDRESS:
The Modbus slave address of the unit. The setup range is
1…247.
•
FACTORY SETTINGS:
Returns all settings to their original values.
ERRORS
The following table lists the functioning of the IM-04DCCT unit in various error situations.
Error
IM
-
04DCCT
ALARM
LEDs
IM
-
04DCCT
ALARM
menu
Alarm
relay
The IM
-
04DCCT unit
without operating voltage
ALM WRN
Insulation fault (R under
InsLimit)
ALARM
Insulat.
ALM
Insulation fault (R under
PrInsLim)
WARN
PreInsul
WRN
The IM
-
04DCCT unit TG
wire is disconnected
STATUS ALARM
Gnd Fail
ALM
The IM
-
04DCCT unit MG
wire is disconnected
STATUS ALARM
Gnd Fail
ALM
System fault (manual
test)
STATUS ALARM
Sys Test
ALM
Alarm relays:
•
ALM insulation alarm
•
WRN insulation pre
-
alarm
Error situations are displayed by means of ALARM LEDs and the alarm menu of the IM
-
04DCCT unit. A blinking LED always means that an alarm is active, and a steady
indicator indicates a fixed and unacknowledged fault.
MODBUS RTU REMOTE CONTROL
When a suitable Modbus address has been set for the IM-04DCCT unit, the device can be
connected to a RS-485 bus. The unit's Modbus RTU slave functionality is now ready for
use. The unit’s Modbus
RTU register map is provided below. The Modbus functions to be
used are Read Holding Registers (0x03) and Write Multiple Registers (0x10).