14
© Copyright Muuntosähkö Oy
–
Trafox
Superintend IMD
The insulation fault alarm has been deactivated but not
acknowledged.
The smallest insulation resistance measured during the fault, the
alarm limit's set value and the fault start time are displayed.
The
Insulat.
and
PreInsul
alarms are active if the measured insulation resistance is
smaller than the alarm or pre-alarm limit.
The
Sys Test
alarm is active if the manual system test fails. In that case, the insulation
resistance can not be measured either, so an insulation resistance alarm is also given.
The
Gnd Fail
alarm is active if the TG or MG wire of the IM-04DCCT unit is disconnected.
In that case, the insulation resistance can not be measured either, so an insulation
resistance alarm is also given.
SETUP MENU
The Setup menu can be used to change system settings, alarm limits, time etc.
The Setup menu is password-protected and accessed as follows:
•
Go to the Setup menu in the main menu. The screen displays “Enter Setup”.
Press T.
•
Change the blinking number with the button and press the button to move
to the next digit. Enter the three digits and press T. After this, you can navigate
the menu with the button.
•
The button takes you to the initial mode.
The password is “123”.
All information on the settings of the device alarm limits and the system are saved in the
internal EEPROM memory of the IM-04DCCT unit.