Interfaces of the function group Encoder-Basic
TR-Electronic GmbH 2013, All Rights Reserved
Printed in the Federal Republic of Germany
Page 96 of 103
TR - ECE - BA - DGB - 0105 - 03
08/31/2017
6.3.4 Saving of parameters, S-0-0264
So that changed parameters are saved permanently, command S-0-0264
Backup working memory
procedure command
must be executed with the value “3”. To reset the command the value “0” must
be written afterwards. At present this parameter is used only internally for the electronic label.
Parameter-Format, Backup working memory procedure command
name
Backup working memory procedure command
attribute length (octet)
2
data type and display format
binary
function
procedure command 0x00 03
positions after decimal point
0
write protection
never
conversion factor
1
scaling / resolution of LSB
1
unit
n/a
minimum value
0
maximum value
3
scope of parameter
local