Installation / Preparation for commissioning
TR-Electronic GmbH 2004, All Rights Reserved
Printed in the Federal Republic of Germany
Page 72 of 115
TR - ECE - BA - DGB - 00036 - 10
10/01/2014
5.2.2 Bus termination
If the measuring system is the last slave
in the PROFIBUS segment, the bus is to
be terminated with the termination
switch = ON. In this state, the
subsequent PROFIBUS is decoupled.
5.2.3 Bus address
Valid PROFIBUS addresses: 3 - 99
10
0
: Setting the 1st position
10
1
: Setting the 10th position
The device does not start up with an
invalid station address.
5.2.4 Shield cover
The shield cover is connected with a special EMC cable gland, whereby the cable
shielding is fitted on the inside.
Prepare the PROFIBUS cable (e.g. 2-wire)
The dimension "X" depends on the type and size of the cable gland.