Object directory
TR-Electronic GmbH 2016, All Rights Reserved
Printed in the Federal Republic of Germany
Page 74 of 153
TR-EMO-BA-GB-0022 v03
09/29/2020
9.2.8 Object 0x1011: Reset Backup Parameters
Object name
Reset Backup Parameters
Object code
ARRAY
Description
This object supports the restoring of the default values of all writable parameters.
Subindex 0: Number of entries
Data type
UNSIGNED8
Attribute
ro
Default
2
Min
-
Max
-
PDO mapping
-
Description
Contains the largest array subindex
Subindex 1: Factory settings for all parameters
Data type
UNSIGNED32
Attribute
rw
Default
0
Min
-
Max
-
PDO mapping
-
Description
Configures all parameters, for which factory settings are
available, with their factory settings. This only occurs if the
value
0x64616F6C
is written. This is the numeric value resulting from the "load"
character string ('l' : 0x6C, 'o': 0x6F, 'a' : 0x61, 'd': 0x64).
Subindex 3: Factory settings for application parameters (0x6xxx-objects)
Data type
UNSIGNED32
Attribute
rw
Default
0
Min
-
Max
-
PDO mapping
-
Description
see subindex 1
Subindex 4: Factory settings for manufacturer-specific parameters (0x2xxx-objects)
Data type
UNSIGNED32
Attribute
rw
Default
0
Min
-
Max
-
PDO mapping
-
Description
see subindex 1