5.5.3 Perform operating mode
If the drive is in the "Ready for operation" state, positioning movements can be
performed. Via the status word (object 0x6041, bit 12: Drive follows the command
value) is displayed that the target values are transferred directly to the controller.
For this purpose the “Cyclic Synchronous Position (CSP)” operating mode must be
set:
Object 0x6060 operating mode = 8
To perform a positioning, object 0x607A must be specified with the target values.
Also see chapter
“Cyclic synchronous modes (operating modes 8, 9, 10)”
on page 137.
5.5.4 Relevant parameters
Figure 13: Cyclic synchronous position control function (CSP)