Index 0x0071: Clear Preset
7.2.4
Danger of physical injury and damage to property due to an actual value
jump during execution of the
Clear Preset – function
!
The
Clear Preset
–
function
should only be executed when the
measuring system is stationary, or the resulting actual value jump must be
permitted by both the program and the application!
By means of parameter
Clear Preset
, the calculated zero-point can be deleted (difference of the
desired adjustment- or preset-value to the physical laser position). After deletion of the zero-point
correction the measuring sys
tem outputs his “real” physical position. With the setting = “Yes” no
Adjustment
and no
Preset function
can be performed. See also chapter
” on page 73 and “Set Position” on page 77.
Index
Subindex
Name
Length
Type
Access
0x0071
0
Clear Preset
8 Bit
UIntegerT
rw
Value
Assignment
Description
Default
0x00
No
Zero-point correction is not deleted
X
0x01
Yes
Zero-point correction is deleted
Index 0x0066: Failure Autoquit
7.2.5
The parameter
Failure Autoquit
determines whether occurring error messages should be cleared
automatically after eliminating the trouble.
Index
Subindex
Name
Length
Type
Access
0x0066
0
Failure Autoquit
8 Bit
UIntegerT
rw
Value
Assignment
Description
Default
0x00
Not Automatically
An occurring error message can be cleared either via
the Control byte bit 2, see page 61, or via the optional
switching input. For the external switching input the
function
Reset Failure Value
must be selected,
see page 73.
0x01
Automatically
An occurring error message is cleared automatically
after remedying of the error.