8.2.6 Object 6010h
– Preset values for multi-sensor devices
Risk of injury and damage to property by an actual value jump when the
Preset adjustment function is performed!
The preset adjustment function should only be performed when the
measuring system is at rest, otherwise the resulting actual value jump must
be permitted in the program and application!
The preset function is used to set the measuring system value of the supported
channels to any position value within the measuring range.
With write access on this object the position value is set to the parameter "Preset
value".
If the value 0xFF FF FF FF is written (sub-index 1 to 3) for the relevant channel the
preset is cleared. Afterwards the position which is output refers to the physical zero
point of the measuring system (delivery status).
Index
0x6010
Object type
Array
Name
Preset values for multi-sensors
Data type
INTEGER32
Category
Mandatory
Preset value, two's complement
Byte 0
Byte 1
Byte 2
Byte 3
2
7
to 2
0
2
15
to 2
8
2
23
to 2
16
2
31
to 2
24
Sub-Index
000
Description
Number of available channels
Access
ro
PDO mapping
no
Default value
3
Value range
0x01…0x03
Sub-Index
001
…003
Description
Preset value position 1 to 3, Preset value channel 1 to 3
Category
Mandatory
Data type
INTEGER32
Access
rw
PDO mapping
no
Default value
0
Value range
-
2 147 483 648…+2 147 483 647 (0x80000000…0x7FFFFFFF)