11.2.2 Object 1003h: Pre-defined Error field, bits 0
– 15
About the Emergency object only the error occurred last is indicated. For each EMCY-
message which could be deleted an EMCY-report with error code "0x0000" is
transmitted. The result can be taken from object 1003h. If no more error is present, the
error register indicates also no more error.
The error list in object 1003h can be deleted in different ways:
1.
Writing a “0” to sub-index 0 in object 1003h
2. Execution of the NMT-
service “Reset Communication”, command 0x82
3. Reading the object 1001h, after the last error was deleted
Error code Meaning
Remedy
0x0000
reset error / no error
-
0x8100
Communication errors, which are
triggered by the CAN-controller.
- Reset node with command 0x81, after that start
the node again with command 0x01.
-
Switch off; switch on again the supply voltage of
the measuring system.
0x8130
Life guard error
-
General bus load ≤ 85 % !
- Attempt to increase the baud rate
- Increase cycle time for node guarding protocol
by means of the objects 100Ch and 100Dh
- Try to restart the device: Voltage OFF/ON.
Heartbeat error
-
General bus load ≤ 85 % !
- Attempt to increase the baud rate
- Adapt cycle time for heartbeat protocol by
means of the objects 1016h or 1017h
Table 11: Emergency Error codes
11.3 Other faults
Fault
Cause
Remedy
Position skips
of the measuring
system
Strong vibrations
Vibrations, impacts and shocks, e.g. on presses, are
dampened with "shock modules". If the error recurs
despite these measures, the measuring system must be
replaced.
Electrical faults
EMC
Perhaps isolated flanges and couplings made of plastic
help against electrical faults, as well as cables with twisted
pair wires for data and supply. Shielding and wire routing
must be performed according to the respective field-bus
system construction guidelines.
Extreme axial and
radial load on the
shaft or a defective
scanning unit.
Couplings prevent mechanical stress on the shaft. If the
error still occurs despite these measures, the measuring
system must be replaced.