7 Parameterization and configuration
WARNING !
Danger of personal injury and damage to property exists if the measuring
system is restarted after positioning in the de-energized state by shifting of the
zero point!
If the number of revolutions is not an exponent of 2, it can occur, if more than 512
revolutions are made in the de-energized state, that the zero point of the multi-turn
measuring system is lost!
•
Ensure that the quotient of
Revolutions Numerator / Revolutions
Denominator
for
a multi-turn measuring system is an exponent of 2 of the group
2
0
, 2
1
, 2
2
…2
12
(1, 2, 4…4096).
or
•
Ensure that every positioning in the de-energized state for a multi-turn measuring
system is within 512 revolutions.
7.1 Configuration Assembly Data Attribute Format
7.1.1 Assembly Object 04h
Instance Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Service
0
Direction
1
Output Code
2
Low Byte
Total Number of Steps
to
5
High Byte
Total Number of Steps
6
Low Byte
Revolutions Numerator
to
9
High Byte
Revolutions Numerator
10
Revolutions Denominator
11
Low Byte
Lower Safety Limit
to
14
High Byte
Lower Safety Limit
15
Low Byte
Lower Operating Limit
to
18
High Byte
Lower Operating Limit
19
Low Byte
Upper Operating Limit
to
22
High Byte
Upper Operating Limit
23
Low Byte
Upper Safety Limit
to
42
26
High Byte
Upper Safety Limit
r/w
Continuation, see following page