Printed in the Federal Republic of Germany
TR-Electronic GmbH 2008, All Rights Reserved
06/27/2017
TR - ECE - BA - DGB - 0073 - 07
Page 125 of 155
7.6.3.5.2 Attribute 0x66/0x67, Revolution Numerator/Divisor
Together, these two parameters
Number of Revolutions Numerator
and
Number of Revolutions Divisor
define the
Number of revolutions
before the
measuring system restarts at zero.
As decimal numbers are not always finite (as is e.g. 3.4), but they may have an infinite
number of digits after the decimal point (e.g. 3.43535355358774...) the number of
revolutions is entered as a fraction.
Attr.-ID
0x66, Numerator
Data type
UDINT
Access
Set / Get
Lower limit
1
Upper limit
256000
Default
4096
Attr.-ID
0x67, Divisor
Data type
UDINT
Access
Set / Get
Lower limit
1 step
Upper limit
256000
Default
4096
Total measuring range = Steps per revolution *
Number of Revolutions
numerator
Number of Revolutions divisor
Formula 2: Gear calculation
Connection path Attr.-ID 0x66,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x66
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #102
Connection path Attr.-ID 0x67,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x67
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #103
So that these attributes are accepted and saved permanently,
0x70 Accept
Parameter
must be performed.