06/12/2019
6 Replacing the measuring system
Ensure that you meet the following requirements while replacing the measuring system:
●
The new measuring system must have the same article number as the measuring system being
replaced; any deviations must be expressly clarified with TR-Electronic.
●
When the new measuring system is used, it must be ensured that the hardware switch settings
comply with the previous settings.
●
The new measuring system must be installed in accordance with the specifications and
requirements in Chapter “Assembly” on Page 20.
●
The new measuring system must be connected in accordance with the specifications in the
interface-specific User Manual.
●
Since the parameters of the measuring system are usually stored in the control, the new
measuring system is parameterized with the projected settings in the start-up phase. If this
mechanism fails, it must be ensured that the settings for the new measuring system are the same
as those for the old one.
●
Depending on the application, the output position value must possibly be adjusted to the reference
position of the machine. The position value must be adjusted as specified in the interface-specific
User Manual.
●
Before the replaced measuring system is recommissioned, its proper functioning must be verified
in a protected test run.