Extending the Safety Program
– Application Examples
TR-Electronic GmbH 2016, All Rights Reserved
Printed in the Federal Republic of Germany
Page 132 of 159
TR - ECE - TI - DGB - 0292 - 01
09/20/2016
5.1.1 Parameter description
Input parameter
Data type Description
REQ
BOOL
Starts the preset adjustment function
NEW_PRES_MULTI
INT
New multi-turn value to be
set.
NEW_PRES_SINGLE
INT
New single-turn value to be
set.
TR_QBAD
BOOL
Passivation bit of the measuring system.
In the example import
F00000_CD_75_-
EPNI/Osafety_1 [DB30002]
from
measuring system F-IO data block.
TR_IPAR_OK
BOOL
Indicates whether the execution of the preset
adjustment function has been completed.
In the example import
F00000_CD_75_-
EPNI/Osafety_1 [DB30002]
from
measuring system F-IO data block.
TR_Pres_Error
BOOL
Indicates whether an error has occurred during
execution of the preset adjustment function.
Import in measuring system input data from
register
TR-Status
at Pin 2
15
.
Output parameter
Data type Description
BUSY
BOOL
Indicates whether the block is currently
executing the preset adjustment function.
VALID
BOOL
Indicates whether the execution of the preset
adjustment function was successfully
completed.
ERROR
BOOL
Indicates whether the execution of the preset
adjustment function ended with an error.
TR_IPAR_EN
BOOL
Sets the measuring system to Ready to
receive for the preset adjustment function.
In the example output
F00000_CD_75_-
EPNI/Osafety_1 [DB30002]
to measuring
system F-IO data block.
TR_Pres_Multi
INT
Preset multi-turn value for the measuring
system. Output in the measuring system
output data to
Preset Multi-Turn
register.
TR_Pres_Single
INT
Preset single-turn value for the measuring
system. Output in the measuring system
output data to
Preset Single-Turn
register.
TR_Pres_Request
BOOL
Ensures transfer of the preset value to the
measuring system.
Output in the measuring system output data to
register
TR-Control1
at Pin 2
0
.