10
WX9 ASD Installation and Operation Manual
Operational and Maintenance
Precautions
•
Turn off and lock-out/tag-out the main power, the control power, and instrumentation connections
before performing any of the following:
• inspecting or servicing the ASD,
• removing any enclosure panels, or
• connecting/disconnecting the power wiring to the equipment.
•
During normal operation, turn the power on only after attaching (or closing) the front cover.
DO
NOT
open or remove the front cover or any of the enclosure panels of the ASD when the power is
on.
•
During system setup, calibration, testing, or troubleshooting, it may be required to access live
circuits.
DO NOT
leave the system unattended and powered with the door(s) and/or covers
removed.
•
If/when taking a live reading (equipment is powered) is required, it shall be performed by
ONLY
. Proper and approved personal protection equipment is to be used by the trained
personnel for all electrical measurements.
•
The capacitors of the ASD maintain a residual charge for a period of time after the ASD is powered
off. The required time for each ASD typeform is indicated with a cabinet label. Ensure that the
ASD power has been turned off and wait at least the minimum time indicated on the enclosure-
mounted label before coming into contact with any circuits.
the system capacitors have completely discharged.
•
DO NOT
attempt to disassemble, modify, or repair the ASD. Contact the TIC Customer Support
Center for repair information.
•
DO NOT
place any objects inside of the ASD — this includes food or liquids.
•
If the ASD should emit smoke, or an unusual odor or sound, turn off the power immediately.
•
The heat sink and other components may become extremely hot to the touch. Allow the unit to cool
before coming into contact with these items.
•
The
Auto-Restart
and
Retry
programmable functions of the ASD may allow for the system to
start or stop unexpectedly. Warning signs to this effect must be clearly posted at or near the
machinery/hazard.
•
Remove power from the ASD during extended periods of non-use.
•
Inspect the system annually (as a minimum) for damaged or improperly functioning parts,
cleanliness, and to ensure that the connectors are tightened securely. Inspect more frequently when
operating in a harsh environment or when used on a high-output-demand application.
DANGER
Содержание WX9 ASD
Страница 1: ...WX9 ASD Install Op Manual TOSHIBA WX9 ASD INSTALLATION OPERATION MANUAL DN 68940 000 March 2014 ...
Страница 2: ......
Страница 3: ...DN 68940 000 March 2014 WX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv WX9 ASD Installation and Operation Manual ...
Страница 213: ...WX9 ASD Installation and Operation Manual 201 Figure 32 WX9 ASD Enclosure Dimensions Dimensions are in in mm ...
Страница 225: ......