Installation Method
1. Model Installation
■
You are required to prepare the ceiling suspension bolts, nuts and washers.
■
Install the unit firmly and horizontally enough to support its weight. (Fig. 1)
■
If you do not fit it firmly, it is not only dangerous but also easily vibrated. If it is
not fitted horizontally, the damper unit becomes defective in operation.
Caution
• When you are required to be cautious on prevention of vibration, we
recommend you to use the anti-vibration ceiling suspension fixtures.
• Never fail to make an inspection opening with
450 mm or more at the place
shown on the paragraph of "Cautions For Operation", so that you can inspect
filters, Heat Exchange Elements, power source and motors.
2. Cautions on Installing The Unit Body Upside
Down
■
Re-fit the ceiling suspension fixture in an opposite side. (If they are left as it is, the foolproof function of ceiling suspension bolts do
not work and will cause the danger of dropping of the unit.)
■
Printed indication is in a reversed position.
In particular, be careful of the arrow mark [
] showing the direction of inserting a Heat Exchange Element.
Electric Works
Have a specialized working contractor perform wiring in accordance with the laws and regulations of the country concerned.
■
Connect the broken lines in the wiring diagram.
■
We recommend that you use a switch having more than 3 mm distance to break contact and more than 15A rated current.
Ceiling Suspension Bolt
(
φ
10 to
φ
12)
Fig. 1
Nut
Washer
Ceiling Suspension
Fixture
Washer
Nut
1 2 3 4 5 6 7
1 2 3 4 5
1 2 3 4 5
1 2 3
5
6 7 8
1
3
5
7 8
1
3
5
7
MS
CN– SAFM
CN– EAFM
CN– DM
NC
NO
CM
3
1
4
1
RY4
CN8
CN6
CN5
CN7
RY5
RY2
RY3
RY4
RY3
RY5
RY2
TM1
4
3
2
1
6
COMMON
L
N
LOW
HIGH
DAMPER
7
5
NO
NC
CM
NO
NC
CM
NO
CM
4
3
2
1
6
7
5
TM1
COMMON
L
N
LOW
HIGH
DAMPER
(1)
(2)
(3)
(4)
(5)
(6)
Model No.
VN-250SE
VN-350SE
VN-500SE
Power Source
(LINE)
(NEUTRAL)
Operation Switch
(1) 0 (OFF)
(2) 1 (ON)
Air Flow Switch
(3) High
(4) Low
Function Select Switch
(5) Heat Exchange
Ventilation
(6) Normal Ventilation
To find out the function of
each switch, refer to Page 8
of the Owner’s manual.
Switch
(To be procured
locally)
(Second main body)
Supply
Air Fan
Red
Orange
Capacitor
Exhaust
Air Fan
Red
Orange
Capacitor
Damper
Motor
Yellow
Low
Blue
High
White
Extra
High
Black
Common
Yellow
Low
Blue
High
White
Extra
High
Black
Common
Bl
ue
Ye
llow
(H
eat
E
xc
han
ge)
Wh
ite
(N
orm
al)
Blac
k
Third main body
Power Source
Model No.
Power Source
VN-250SE
220-240V~50Hz/
220V~60Hz
VN-350SE
VN-500SE
Model No.
Capacitor
VN-250SE
2.0
µ
F 450VAC
VN-350SE
3.0
µ
F 450VAC
VN-500SE
3.5
µ
F 450VAC
FY250_CON-EN.fm Page 5 Friday, June 7, 2002 7:19 PM