7. Operating using external signals
7-14
4
4
4
7
9
You can input voltage signals and current signals to the analog input terminals as a frequency command.
7. 3. 1
Inputting frequency commands by analog signals
You can select four types of analog signals as a frequency command signal.
• Potentiometer
• 0 - 10 Vdc
• 4(0) - 20 mAdc
• -10 to +10 Vdc
For how to fine adjust the analog signals and output frequencies, refer to [6. 6. 3].
■
Configuration of the control terminal block
■
Analog input terminal function settings
7. 3
Frequency commands by the analog
signals
Terminal
symbol
Title
Parameter name
Adjustment range
Default
setting
RR
F201
RR point 1 input value
0 - 100 (%)
0
F202
RR point 1 frequency
0.0 - 590.0 (Hz)
0.0
F203
RR point 2 input value
0 - 100 (%)
100
F204
RR point 2 frequency
0.0 - 590.0 (Hz)
50.0/60.0
*1