6. [Advanced] How to use parameters
3
4
6
9
<F910: PM step-out detection current level>
<F911: PM step-out detection time>
■
Function
If the PM motor steps out and if the exciting current increases (it increases in such a case) and
remains over the value set by <F910: PM step-out detection current level > for the period of time set
by <F911: PM step-out detection time>, the inverter will judge the motor to be stepping out and trip
it.
At that time, the trip message "SOUT" is displayed.
■
Parameter setting
6. 39 Step-out detection of PM motor
Title
Parameter name
Adjustment range
Unit
Default setting
F910
PM step-out detection
current level
1 - 150
%
100
F911
PM step-out detection
time
0.00: Disabled
0.01 - 2.55
s
0.00
Important
• When using an PM motor, consult your Toshiba distributor, since the inverter is not compatible
with all types of PM motors.
• The inverter may fail to detect step-out in some cases, because it uses an electrical method to
detect step-out. To avoid detection failures, you are recommended to install a mechanical step-
out detector.
Memo
• For setting of PM motor parameter, refer to [6. 23. 2].
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
0.0Hz
STOP
16:44
F910 : PM step-out current level
Min: 1
Max: 150
X1000
X100
X10
X1
%
100
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...