6. [Advanced] How to use parameters
3
4
6
9
6. 34. 8 Clearing run command
<F719: Run command clear select>
■
Function
This parameter is used to select whether the run command is retained or cleared when the following
events occur during panel run or RS485 communication run.
• Coast stop with standby function (ST) is off (OFF display)
• Coast stop with coast command function (FRR) is on (OFF display)
• Power circuit undervoltage (MOFF) alarm
■
Parameter setting
■
Difference between the settings
Title
Parameter name
Adjustment range
Default setting
F719
Run command clear
select
0: Clear at coast stop. Retain when MOFF
occurs and CMOd is changed.
1: Retain run command.
2: Clear at coast stop and at MOFF. Retain
when CMOd is changed.
3: Clear at coast stop, at MOFF and when
CMOd is changed.
2
<F719> setting value
Coast stop
When power circuit
undervoltage (MOFF)
alarm occurred
When <CMOd> is
changed
0
Run command clear
Retain run command
1
Retain run command
2
Run command clear
Retain run command
3
Run command clear
Important
• If "PrA" alarm occurs when STO activated, run command is cleared regardless of the <F719>
setting.
0: Clr at coast stop
1: Retain run command
0.0Hz
STOP
14:14
F719 : Run command clear select
2: Clr at coast stop & MOFF
3: Clr at coast stop, MOFF & Cmod
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...