E6582062
6-85
6. [Advanced] How to use parameters
3
4
6
9
Check the motor name plate and set the following parameters first.
- <vL: Base frequency 1> (Rated frequency)
- <vLv: Base frequency voltage 1> (Rated voltage)
- <F405: Motor rated capacity>
- <F415: Motor rated current>
- <F417: Motor rated speed>
Next, set <Pt: V/f Pattern>. For details of setting methods, refer to [5. 3. 4].
Then, select <F400> = "4: Motor parameters auto calculation (0 after execution)" and calculate
motor parameters automatically.
Motor parameters <F402: Automatic torque boost>, <F412: Leakage inductance>, and <F416:
Motor no load current> will be set automatically.
This setting can be made without connecting the motor since it only calculates.
After automatic setting of motor parameter with <F400> = "4", be sure to set <F400> to "2: Auto-
tuning at run command (0 after execution)" and perform an auto-tuning.
You can set <F400> to "4" and "2" collectively by setting <F400> to "5: 4+2 (0 after excecution)".
Since calculation is performed based on general trend, the calculation results may not be correct. In
this case, set the parameter manually. In case ETN3 trip occurs after set 4 to F400 , do not set 4 to
F400, and set the parameter manually.
■
Setting method 4: Manually setting motor parameter
Set <Pt: V/f Pattern> and set the motor parameter manually.
If tuning error "Etn1" is displayed during auto-tuning setting or when you want to improve vector
control characteristics, set motor parameters individually.
4) Parameter setting
Title
Parameter name
Adjustment range
Unit
Default setting
F401
Slip frequency gain
0 - 250
%
70
F402
Automatic torque boost
0.1 - 30.00
%
*1
F405
Motor rated capacity
0.01 - 315.0
kW
F412
Leakage inductance
0.0 - 25.0
%
F413
Exciting current
coefficient
100 - 150
%
100
F415
Motor rated current
A
F416
Motor no load current
10 - 90
%
F417
Motor rated speed
100 - 64000
min
-1
*2
F459
Load inertia ratio
0.1 - 100.0
Times
1.0
F460
Speed control response
1
0.0 - 25.0
-
0.0
F461
Speed control
stabilization coefficient 1
0.50 - 2.50
-
1.00
F462
Speed reference filter
coefficient 1
0 - 100
-
35
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...