6. [Advanced] How to use parameters
6-34
4
4
6
9
6. 7. 3
Setting a frequency command to 0 Hz securely
<F244: 0 Hz dead band>
■
Function
Set the frequency command to 0 Hz when it is under the setting value of <F244: 0 Hz dead band>.
This function is used to securely set the frequency command to 0 Hz in the following case: although
an analog signal is set to 0 Hz in order to use the vector control with a sensor to fix the motor shaft,
it does not become 0 Hz due to a drift or offset.
■
Parameter setting
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3]
Title
Parameter name
Adjustment range
Unit
Default setting
F244
0 Hz dead band
0.0 - 5.0
Hz
0.0
Memo
• This function is invalid for a preset speed frequency command.
• It is valid for frequency commands which are prioritized in <FMOd: Frequency command
selection 1>, <F207: Frequency command selection 2>, and communications.
• For the override function, values are added or multiplied for frequencies with this function
enabled.
0.0Hz
STOP
13:03
F244 : 0 Hz dead band
Min: 0.0
Max: 5.0
X1000
X100
X10
X1
Hz
0.0
Frequency command value
Output value after processing
frequency command dead band
0Hz
<F244>
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...