6. [Advanced] How to use parameters
3
4
6
9
6. 7. 2
Run/stop with a frequency command
<F241: Run frequency>
<F242: Run frequency hysteresis>
■
Function
You can run/stop the motor with only a frequency command when a run command remains ON.
When the frequency command reaches the set frequency value, the inverter will start to run. When it
becomes below the set value, the inverter will stop.
■
Parameter setting
■
Setting method
When the frequency command reaches the setting value of <F241: Run frequency>, the inverter will
start to run. When the command becomes below the setting value, the inverter will stop.
To prevent the inverter from repeatedly running/stopping around the frequency set with <F241: Run
frequency>, use <F242: Run frequency hysteresis> to provide hysteresis.
Set the parameter, referring to the following figure.
Reference
• How to operate the operation panel -> Refer to [3. 1. 1].
• How to switch display mode on the operation panel -> Refer to [3. 1. 2].
• Procedure to change parameter setting -> Refer to [4. 2. 3].
Title
Parameter name
Adjustment range
Unit
Default setting
F241
Run frequency
0.0 - FH
Hz
0.0
F242
Run frequency hysteresis
0.0 - FH
Hz
0.0
0.0Hz
STOP
13:01
F241 : Run frequency
Min: 0.0
Max: 80.0
X1000
X100
X10
X1
Hz
0.0
Output frequency (Hz)
Frequency command
0
A
B
100%
<FH>
<F241>
<F242>
<F242>
<F241>
<F241>
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...