6. 1. 3
Output a signal when reached to a specified
frequency (output the specified frequency
attainment signal)
<F101: Reach signal specified frequency>
<F102: Reach signal detection band>
■
Function
When the output frequency becomes the frequency that is equal to the value for <F101: Reach
signal specified frequency> plus or minus the value for <F102: Reach signal detection band>, the
ON signal (specified frequency attainment signal) is output from a specified output terminal.
■
Parameter setting
■
Output terminal parameter setting
When you want to output the specified frequency attainment signal to the output terminal [FP], set
"8" for <F130: Terminal FP function 1>.
When you want to output the signal from the relay logic output terminals [FLA]-[FLB]-[FLC], set
<F132: Terminal FL function>. When you want to output the signal from the [R1A]-[R1C] terminals,
set <F133: Terminal R1 function 1>. When you want to output the signal from the terminals [R2A]-
[R2C] set <F134: Terminal R2 function >.
Title
Parameter name
Adjustment range
Unit
Default setting
F101
Reach signal specified
frequency
0.0-FH
Hz
0.0
F102
Reach signal detection
band
0.0-FH
Hz
2.5
0.0Hz
STOP
12:45
F101 : Reach signal frequency
Min: 0.0
Max: 80.0
X1000
X100
X10
X1
Hz
0.0
ON
OFF
Output frequency (Hz)
Time (s)
Output terminal
(Specified frequency
attainment)
ON
OFF
Terminal [F]
(Fwd run)
0
<F101>
<F102>
<F101>
<F102>
<F101>
Содержание TOSVERT VF-AS3
Страница 2: ...1 9 ...
Страница 14: ......
Страница 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Страница 18: ......
Страница 34: ......
Страница 438: ......
Страница 458: ......
Страница 470: ......
Страница 482: ......
Страница 502: ......
Страница 572: ......
Страница 590: ......
Страница 608: ......
Страница 616: ......
Страница 618: ......
Страница 620: ......
Страница 621: ...1 3 9 10 ...